Energy and payback
What a compressed air leak costs
Leak size, line pressure, hours, and the power rate in; the air lost, the compressor power it takes, and the dollars a year, per leak and for the plant.
Read the guide: what the number means and how to use it
- Leak flow from the orifice table in the U.S. DOE / Compressed Air Challenge fact sheet: at 100 psig a 1/16 in. hole passes about 6.5 cfm, 1/8 in. 26, 1/4 in. 104, 3/8 in. 234; scaled by absolute pressure for other line pressures.
- Compressor power = cfm × specific power (kW per 100 cfm); energy = kW × hours; cost at the rate.
Need it quoted?
See what the first-year deduction does to the payback on the same purchase.
Section 179Compressed air leak cost
Cost per leak per year
3,370 $
Cost of 10 leaks per year
33,696 $
Air lost per leak
26 cfm
at 100 psig
- 260 cfm of leaks is a compressor's worth; a leak survey with an ultrasonic detector pays back in weeks.
- Compressor power per leak
- 4.68 kW
- kWh per leak per year
- 28,080
One line for the file or the vendor
0.125" leak at 100 psig: 26 cfm, 4.68 kW, $3370/yr at 6000 h and $0.12/kWh; 10 leaks: $33,696/yr.
How it is figured
- Leak flow from the orifice table in the U.S. DOE / Compressed Air Challenge fact sheet: at 100 psig a 1/16 in. hole passes about 6.5 cfm, 1/8 in. 26, 1/4 in. 104, 3/8 in. 234; scaled by absolute pressure for other line pressures.
- Compressor power = cfm × specific power (kW per 100 cfm); energy = kW × hours; cost at the rate.
How to find the leaks
- 1. Walk the plant during a quiet shift with an ultrasonic leak detector, or soapy water on fittings; tag each leak with its size and location.
- 2. Read the line pressure at the header gauge.
- 3. Compressor hours from its hour meter or the control panel; the specific power from its data sheet (or 18 kW per 100 cfm for a rotary screw).
Tools: ultrasonic leak detector (rent one), tags, the compressor's hour meter
Sources: U.S. DOE, Compressed Air Tip Sheet 3: Minimize Compressed Air Leaks (leak flow table); Compressed Air Challenge, Best Practices for Compressed Air Systems. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- How much of a plant's air is leaks?
- DOE surveys put it at 20 to 30% of compressor output in plants without a leak program, and under 10% with one. A dozen 1/8 in. leaks at 100 psig cost about as much as running a 25 hp compressor for nothing.
Related calculators: Air compressor sizing, Electricity cost, Simple payback. All calculators.