Evaporative cooler CFM: the guide

An evaporative cooler is a fan and a wet pad, and it cools by moving a lot of outside air once through the building; the sizing is air changes a minute, and the cooling it delivers is set by the humidity outside.

Open the calculator

Why this number matters

Air passing through a wet pad gives up heat to evaporate water and comes out cooler and more humid: about 80% of the way from the dry bulb to the wet bulb temperature. In Phoenix that is 25°F of cooling; in Detroit on a design day about 16; on a muggy day with the wet bulb near 78 it is under 10, which is why the Southwest runs evaporative cooling everywhere and the Midwest runs it in shops and warehouses where a few degrees and a breeze are enough.

Because the air is cooled once and then exhausted, the sizing is in minutes per air change rather than changes per hour: two minutes for an ordinary shop, one for a foundry or a bakery, three for light work. The cfm is the volume over that, the coolers are the cfm over the unit's rating, and the air needs a way out, relief openings sized at about 500 feet per minute, or the building pressurizes and the fans stall.

The water use, the pad maintenance, and the humidity added to the building are the costs; for a warehouse that stores nothing moisture-sensitive they are small against mechanical cooling.

How it is figured

  • cfm = volume ÷ minutes per air change (evaporative cooling needs 1 to 3 minute air changes because the air is only cooled once, then exhausted). Units = cfm ÷ the cooler's rating.
  • Supply temperature = dry bulb − 0.8 × (dry bulb − wet bulb), the usual 80% pad saturation. Relief openings pass the same cfm at about 500 fpm.

A worked example

A 150 by 100 by 24 foot shop at a two-minute air change needs 180,000 cfm, eighteen 10,000-cfm coolers, and 360 square feet of relief opening; at a 92/72°F design day the supply air is about 76°F.

The tool's starting values, and what it returns for them:

Length150 ft
Width100 ft
Ceiling height24 ft
Minutes per air change2, typical warehouse or shop
Cooler rating10,000 cfm
Outdoor design dry bulb92 °F
Outdoor design wet bulb72 °F
Cooling airflow180,000 cfm
Coolers18
Supply air temperature76 °F
Relief opening360 sq ft free area
Wet bulb depression20 °F

Mistakes that catch people

  • No relief openings; the building pressurizes and the coolers deliver nothing.
  • Expecting it to work in a humid climate's worst week.
  • Sizing by square feet of floor instead of volume and air change.

Rules of thumb

  • 1 to 3 minutes per air change: 1 for high heat, 2 for shops and warehouses, 3 for light work.
  • Cooling ≈ 0.8 × (dry bulb − wet bulb).
  • Relief openings: cfm ÷ 500 square feet.

When to stop calculating and make a call

  • Humidity-sensitive product or processes: the added moisture is the first question.
  • Combined with HVLS fans: the fans distribute the cooled air and the two are designed together.

Questions people ask

Does evaporative cooling work in the Midwest?
On most summer days, yes: a 92/72°F design gives about 16°F of cooling and the air moves fast, which feels cooler still. On the muggy days with wet bulbs near 78 it drops to under 10°F; the Southwest gets 25 to 30.

Standards and sources

  • ASHRAE Handbook, HVAC Systems and Equipment, Evaporative Air-Cooling Equipment
  • Evaporative cooler manufacturer sizing guides (Portacool, Big Ass Fans, Breezair)

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.