Evaporative cooler size for a shop or warehouse

Space size and how hot it runs in; the cfm of evaporative cooling, the units, the relief opening, and the temperature drop your humidity allows.

Read the guide: what the number means and how to use it

  • cfm = volume ÷ minutes per air change (evaporative cooling needs 1 to 3 minute air changes because the air is only cooled once, then exhausted). Units = cfm ÷ the cooler's rating.
  • Supply temperature = dry bulb − 0.8 × (dry bulb − wet bulb), the usual 80% pad saturation. Relief openings pass the same cfm at about 500 fpm.

Need it quoted?

HVLS fans, unit heaters, and ventilation priced with installation as line items.

Request a quote

Evaporative cooler CFM

cooling cfm180,000 cfm

Cooling airflow

180,000 cfm

360,000 cu ft every 2 min

Coolers

18

at 10,000 cfm each

Supply air temperature

76 °F

16°F drop at 80% pad efficiency

Relief opening
360 sq ft free areaopen doors, louvers, or relief dampers at 500 fpm
Wet bulb depression
20 °F

One line for the file or the vendor

150x100x24 ft at 2 min per air change: 180,000 cfm, 18 coolers at 10,000 cfm, supply 76°F at 92/72°F design, 360 sq ft relief.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • cfm = volume ÷ minutes per air change (evaporative cooling needs 1 to 3 minute air changes because the air is only cooled once, then exhausted). Units = cfm ÷ the cooler's rating.
  • Supply temperature = dry bulb − 0.8 × (dry bulb − wet bulb), the usual 80% pad saturation. Relief openings pass the same cfm at about 500 fpm.

Sources: ASHRAE Handbook, HVAC Systems and Equipment, Evaporative Air-Cooling Equipment; Evaporative cooler manufacturer sizing guides (Portacool, Big Ass Fans, Breezair). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Does evaporative cooling work in the Midwest?
On most summer days, yes: a 92/72°F design gives about 16°F of cooling and the air moves fast, which feels cooler still. On the muggy days with wet bulbs near 78 it drops to under 10°F; the Southwest gets 25 to 30.