Air, heating, and ventilation
Evaporative cooler size for a shop or warehouse
Space size and how hot it runs in; the cfm of evaporative cooling, the units, the relief opening, and the temperature drop your humidity allows.
Read the guide: what the number means and how to use it
- cfm = volume ÷ minutes per air change (evaporative cooling needs 1 to 3 minute air changes because the air is only cooled once, then exhausted). Units = cfm ÷ the cooler's rating.
- Supply temperature = dry bulb − 0.8 × (dry bulb − wet bulb), the usual 80% pad saturation. Relief openings pass the same cfm at about 500 fpm.
Need it quoted?
HVLS fans, unit heaters, and ventilation priced with installation as line items.
Request a quoteEvaporative cooler CFM
Cooling airflow
180,000 cfm
360,000 cu ft every 2 min
Coolers
18
at 10,000 cfm each
Supply air temperature
76 °F
16°F drop at 80% pad efficiency
- Relief opening
- 360 sq ft free areaopen doors, louvers, or relief dampers at 500 fpm
- Wet bulb depression
- 20 °F
One line for the file or the vendor
150x100x24 ft at 2 min per air change: 180,000 cfm, 18 coolers at 10,000 cfm, supply 76°F at 92/72°F design, 360 sq ft relief.
How it is figured
- cfm = volume ÷ minutes per air change (evaporative cooling needs 1 to 3 minute air changes because the air is only cooled once, then exhausted). Units = cfm ÷ the cooler's rating.
- Supply temperature = dry bulb − 0.8 × (dry bulb − wet bulb), the usual 80% pad saturation. Relief openings pass the same cfm at about 500 fpm.
Sources: ASHRAE Handbook, HVAC Systems and Equipment, Evaporative Air-Cooling Equipment; Evaporative cooler manufacturer sizing guides (Portacool, Big Ass Fans, Breezair). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Does evaporative cooling work in the Midwest?
- On most summer days, yes: a 92/72°F design gives about 16°F of cooling and the air moves fast, which feels cooler still. On the muggy days with wet bulbs near 78 it drops to under 10°F; the Southwest gets 25 to 30.
Related calculators: HVLS fan sizing, Air changes and exhaust CFM, Fan cooling effect. All calculators.