Air, heating, and ventilation
How much cooler a fan makes it feel
Air speed at the person in; the perceived temperature drop and the effective temperature, from the ASHRAE 55 elevated air speed comfort offset.
Read the guide: what the number means and how to use it
- Perceived cooling from moving air, fitted to the ASHRAE Standard 55 elevated air speed comfort limits: about 4°F at 160 fpm (1.8 mph) and 5°F at 240 fpm (2.7 mph), flattening toward 7°F at high speeds.
- Above 70% humidity the evaporative part of the effect shrinks, taken here as 0.05°F per point over 70.
Need it quoted?
HVLS fans, unit heaters, and ventilation priced with installation as line items.
Request a quoteFan cooling effect
Feels cooler by
5.2 °F
Feels like
84.8 °F
at 3 mph
Air speed
264 fpm
One line for the file or the vendor
90°F at 50% RH with 3 mph air: feels about 5.2°F cooler, 84.8°F.
How it is figured
- Perceived cooling from moving air, fitted to the ASHRAE Standard 55 elevated air speed comfort limits: about 4°F at 160 fpm (1.8 mph) and 5°F at 240 fpm (2.7 mph), flattening toward 7°F at high speeds.
- Above 70% humidity the evaporative part of the effect shrinks, taken here as 0.05°F per point over 70.
Sources: ASHRAE Standard 55, Thermal Environmental Conditions for Human Occupancy, elevated air speed (Section 5.3.3). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Does a fan lower the air temperature?
- No. It makes people feel cooler by moving heat and moisture off the skin, which is why the number is a perceived offset. The air temperature is unchanged, and an empty room gains nothing.
- Why do fan makers quote 10°F?
- Some do, at high speeds with low humidity on an active worker. The ASHRAE comfort basis used here is more conservative, 4 to 6°F in the speeds HVLS fans deliver on a warehouse floor.
Related calculators: HVLS fan sizing, Destratification savings, Air changes and exhaust CFM. All calculators.