Air, heating, and ventilation

Heating saved by destratification fans

Ceiling height, the floor and ceiling temperatures now, and the heating bill in; the stratification, the average temperature cut by mixing the air, and the heating saved.

Read the guide: what the number means and how to use it

  • Stratification is the ceiling temperature less the floor temperature. Before mixing, the average air temperature is about the midpoint; after, the whole column sits a degree or two above the floor setpoint.
  • Heat loss through the roof and walls follows the inside air temperature, so cutting the average cuts the loss: taken as 3% of heating energy per °F of average reduction, capped at 30%, the range reported for destratification fans.

Need it quoted?

HVLS fans, unit heaters, and ventilation priced with installation as line items.

Request a quote

Destratification savings

stratification °F20average cut °F8.5saving %26

Heating saved per year

6,120 $

about 26% of the bill

Stratification now

20 °F

0.67°F per foot of height

Average air temperature cut

8.5 °F

70°F average to about 62°F

Saving
26 %

One line for the file or the vendor

30 ft deck, 60°F floor / 80°F ceiling (20°F stratified): mixing cuts the average 8.5°F, about 26% or $6,120 of a $24,000 heating bill.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Stratification is the ceiling temperature less the floor temperature. Before mixing, the average air temperature is about the midpoint; after, the whole column sits a degree or two above the floor setpoint.
  • Heat loss through the roof and walls follows the inside air temperature, so cutting the average cuts the loss: taken as 3% of heating energy per °F of average reduction, capped at 30%, the range reported for destratification fans.

How to measure stratification

  1. 1. On a cold morning with the heat running, read the thermostat or a thermometer at 5 ft for the floor temperature.
  2. 2. Read the air temperature at the deck: a probe thermometer on a pole or lift, or an infrared thermometer on the underside of the roof deck as a proxy.
  3. 3. Note the heating bill for the last 12 months from the gas or electric statements.

Tools: probe thermometer and a pole, or an infrared thermometer; the utility bills

Sources: U.S. DOE / Federal Energy Management Program, destratification fan guidance; Rule of thumb: about 3% heating energy per °F of indoor temperature (ENERGY STAR building guidance). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

How much warmer is the ceiling than the floor?
In a 30 ft warehouse heated by unit heaters, 15 to 25°F is common: warm air rises and sits under the deck, where it leaks out through the roof at the highest rate. Destratification fans or HVLS fans run slowly bring it back down.
Is 30% realistic?
It is the top of the range in field studies, for tall unmixed buildings with a lot of roof. 10 to 20% is the usual outcome; the calculator ties the estimate to the stratification you actually measure.

Related calculators: HVLS fan sizing, Warehouse heater BTU, Metal roof condensation. All calculators.