Air, heating, and ventilation
Heating saved by destratification fans
Ceiling height, the floor and ceiling temperatures now, and the heating bill in; the stratification, the average temperature cut by mixing the air, and the heating saved.
Read the guide: what the number means and how to use it
- Stratification is the ceiling temperature less the floor temperature. Before mixing, the average air temperature is about the midpoint; after, the whole column sits a degree or two above the floor setpoint.
- Heat loss through the roof and walls follows the inside air temperature, so cutting the average cuts the loss: taken as 3% of heating energy per °F of average reduction, capped at 30%, the range reported for destratification fans.
Need it quoted?
HVLS fans, unit heaters, and ventilation priced with installation as line items.
Request a quoteDestratification savings
Heating saved per year
6,120 $
about 26% of the bill
Stratification now
20 °F
0.67°F per foot of height
Average air temperature cut
8.5 °F
70°F average to about 62°F
- Saving
- 26 %
One line for the file or the vendor
30 ft deck, 60°F floor / 80°F ceiling (20°F stratified): mixing cuts the average 8.5°F, about 26% or $6,120 of a $24,000 heating bill.
How it is figured
- Stratification is the ceiling temperature less the floor temperature. Before mixing, the average air temperature is about the midpoint; after, the whole column sits a degree or two above the floor setpoint.
- Heat loss through the roof and walls follows the inside air temperature, so cutting the average cuts the loss: taken as 3% of heating energy per °F of average reduction, capped at 30%, the range reported for destratification fans.
How to measure stratification
- 1. On a cold morning with the heat running, read the thermostat or a thermometer at 5 ft for the floor temperature.
- 2. Read the air temperature at the deck: a probe thermometer on a pole or lift, or an infrared thermometer on the underside of the roof deck as a proxy.
- 3. Note the heating bill for the last 12 months from the gas or electric statements.
Tools: probe thermometer and a pole, or an infrared thermometer; the utility bills
Sources: U.S. DOE / Federal Energy Management Program, destratification fan guidance; Rule of thumb: about 3% heating energy per °F of indoor temperature (ENERGY STAR building guidance). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- How much warmer is the ceiling than the floor?
- In a 30 ft warehouse heated by unit heaters, 15 to 25°F is common: warm air rises and sits under the deck, where it leaks out through the roof at the highest rate. Destratification fans or HVLS fans run slowly bring it back down.
- Is 30% realistic?
- It is the top of the range in field studies, for tall unmixed buildings with a lot of roof. 10 to 20% is the usual outcome; the calculator ties the estimate to the stratification you actually measure.
Related calculators: HVLS fan sizing, Warehouse heater BTU, Metal roof condensation. All calculators.