Air, heating, and ventilation
Heater size for a warehouse or shop, BTU/h
Building size, how well it is insulated, the inside and outside design temperatures, and the dock door traffic in; the heat loss in BTU/h and the unit heaters to cover it.
Read the guide: what the number means and how to use it
- Envelope and normal infiltration: volume × temperature difference × a construction factor (BTU/h per cu ft per °F), the unit heater makers' quick method: 0.133 bare metal, down to 0.035 for a well insulated, tight building.
- Each working dock door adds about 1,500 cfm of infiltration a quarter of the time: 1.08 × cfm × ΔT × 0.25.
Need it quoted?
HVLS fans, unit heaters, and ventilation priced with installation as line items.
Request a quoteWarehouse heater BTU
Heat loss at design
2,449,800 BTU/h
Unit heaters
16
200,000 BTU/h input each at 80% efficiency
Per square foot
122.5 BTU/h per sq ft
- Walls, roof, and infiltration
- 2,304,000 BTU/h
- Dock door infiltration
- 145,800 BTU/h
- Output per heater
- 160,000 BTU/h
- If electric
- 718 kW
One line for the file or the vendor
200x100x24 ft, factor 0.08, 60°F in / 0°F out, 6 doors: 2,449,800 BTU/h; 16 × 200,000 BTU/h unit heaters.
How it is figured
- Envelope and normal infiltration: volume × temperature difference × a construction factor (BTU/h per cu ft per °F), the unit heater makers' quick method: 0.133 bare metal, down to 0.035 for a well insulated, tight building.
- Each working dock door adds about 1,500 cfm of infiltration a quarter of the time: 1.08 × cfm × ΔT × 0.25.
- Gas unit heaters deliver about 80% of input; the count is the total over that output, rounded up. Spread them to cover the doors and the far corners.
What to gather
- 1. Building dimensions and eave height.
- 2. Insulation from the drawings or the blanket facing tag; a compressed R-19 performs like light insulation.
- 3. The outside design temperature for the site from the ASHRAE climatic data or the local code (the 99% winter value), and the temperature the work needs inside.
Tools: the drawings, ASHRAE design temperatures for the nearest station
Sources: Modine / Reznor unit heater sizing guides (volume × ΔT × factor method); ASHRAE Handbook, Fundamentals, Climatic Design Information (99% heating design temperatures). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Is this a heat loss calculation?
- It is the quick method unit heater makers publish for budgeting. A full load calculation (ASHRAE or Manual N) itemizes each wall, roof, slab edge, and the real infiltration and will land within about 15% of this for an ordinary metal building; use it to size a budget and sanity-check a bid.
- Why does the dock matter so much?
- An open door with a trailer at it moves a lot of air. Dock seals or shelters, fast doors, and air curtains cut that term, and infrared heaters at the doors warm the people and the floor rather than the air that leaves.
Related calculators: Destratification savings, Electric heat kW, BTU, amps, Metal roof condensation. All calculators.