Warehouse heater BTU: the guide

Heater sizing is a heat loss estimate: how fast the building loses BTUs on the coldest design night, plus what the dock doors let in while trailers are worked.

Open the calculator

Why this number matters

The unit heater makers publish a quick method that has sized warehouses for decades: the building volume times the design temperature difference times a factor for how well it is built, from 0.133 BTU/h per cubic foot per degree for bare metal down to 0.035 for a tight, well-insulated building. It folds the walls, the roof, and ordinary infiltration into one number and lands within about 15% of a full calculation for an ordinary metal building. Dock doors are added separately because a working door with a trailer at it moves far more air than the rest of the building.

The design temperature is the site's 99% winter figure, the temperature it is colder than only 1% of the hours: about 0°F in Michigan, 10 in Ohio, −10 in Minnesota. Sizing to the record low buys heaters that short-cycle all winter. Gas unit heaters deliver about 80% of their input, so a 200,000 BTU input heater is 160,000 of heat, and the count is spread so the doors and the far corners each have one.

The dock term is the lever. Dock seals, a fast door, and an air curtain on the busy positions cut it, and infrared heaters aimed at the dock floor warm the people and the slab instead of the air that leaves with the trailer.

How it is figured

  • Envelope and normal infiltration: volume × temperature difference × a construction factor (BTU/h per cu ft per °F), the unit heater makers' quick method: 0.133 bare metal, down to 0.035 for a well insulated, tight building.
  • Each working dock door adds about 1,500 cfm of infiltration a quarter of the time: 1.08 × cfm × ΔT × 0.25.
  • Gas unit heaters deliver about 80% of input; the count is the total over that output, rounded up. Spread them to cover the doors and the far corners.

A worked example

A 200 by 100 by 24 foot lightly insulated building at 60°F inside and 0 outside loses about 2.3 million BTU/h through the envelope; six working dock doors add about 240,000. At 80% efficiency that is 16 unit heaters of 200,000 BTU/h input, or about 12.7 BTU/h per square foot.

The tool's starting values, and what it returns for them:

Building length200 ft
Building width100 ft
Eave height24 ft
InsulationLight: R-10 to R-13 blankets
Inside design temperature60 °F
Outside design temperature0 °F
Dock doors in use6
Unit heater size200,000 BTU/h
Heat loss at design2,449,800 BTU/h
Unit heaters16
Per square foot122.5 BTU/h per sq ft
Walls, roof, and infiltration2,304,000 BTU/h
Dock door infiltration145,800 BTU/h
Output per heater160,000 BTU/h
If electric718 kW

What to gather

  1. Building dimensions and eave height.
  2. Insulation from the drawings or the blanket facing tag; a compressed R-19 performs like light insulation.
  3. The outside design temperature for the site from the ASHRAE climatic data or the local code (the 99% winter value), and the temperature the work needs inside.

Tools: the drawings, ASHRAE design temperatures for the nearest station

Mistakes that catch people

  • Sizing to the record low instead of the design temperature.
  • Forgetting that a draped blanket is 'light' insulation, not 'average', once it is compressed over purlins.
  • Hanging all the heaters in the middle and leaving the dock cold.

Rules of thumb

  • Factors: bare metal 0.133, light 0.08, average 0.055, good 0.035 BTU/h per cu ft per °F.
  • Gas unit heaters: 80% of input is output.
  • A working dock door is worth about 1,500 cfm of infiltration a quarter of the time.

When to stop calculating and make a call

  • Buying the system: the HVAC contractor's load calculation itemizes walls, roof, slab edge, and real infiltration.
  • Makeup air units, radiant systems, and anything with combustion air in a tight building: a mechanical design.

Questions people ask

Is this a heat loss calculation?
It is the quick method unit heater makers publish for budgeting. A full load calculation (ASHRAE or Manual N) itemizes each wall, roof, slab edge, and the real infiltration and will land within about 15% of this for an ordinary metal building; use it to size a budget and sanity-check a bid.
Why does the dock matter so much?
An open door with a trailer at it moves a lot of air. Dock seals or shelters, fast doors, and air curtains cut that term, and infrared heaters at the doors warm the people and the floor rather than the air that leaves.

Standards and sources

  • Modine / Reznor unit heater sizing guides (volume × ΔT × factor method)
  • ASHRAE Handbook, Fundamentals, Climatic Design Information (99% heating design temperatures)

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.