Electrical · guide
Electric heat kW, BTU, amps: the guide
Electric heat is the one load where every watt is heat and the power factor is one; the conversion is fixed, and the circuit follows the 125% continuous rule.
Why this number matters
A kilowatt of electric resistance heat delivers 3,412 BTU per hour, every time, with no efficiency to argue about. The current is the watts divided by the volts, with the square root of three for three phase, and because fixed electric heat is a continuous load the conductors and breaker are sized at 125% of it. A 10 kW three-phase 480-volt heater draws 12 amps and sits on a 15- or 20-amp breaker; the same heater at single-phase 240 draws 42 amps and needs a 60.
What electric heat costs is the other half of the picture. At 12 cents a kilowatt-hour it is about $35 per million BTU, against $12 to $18 for natural gas at typical efficiencies, which is why it is the heater for the small, intermittent, or gas-less space and the infrared choice for a dock door, where it heats the people and the floor rather than the air that leaves.
Unit heater sizing itself comes from the building's heat loss; this converter gives the circuit for a heater you have already chosen.
How it is figured
- 1 kW = 3,412 BTU/h; resistance heat converts all of it. Amps = watts ÷ volts (single phase) or ÷ (volts × 1.732) (three phase); power factor 1.0.
- Fixed electric space heating is a continuous load: conductors and breaker at 125% (NEC 424.3(B)).
A worked example
A 10 kW heater delivers 34,120 BTU/h; at 480 volts three phase it draws 12 amps, is designed at 15 amps, and goes on a 20-amp breaker with 12 AWG copper.
The tool's starting values, and what it returns for them:
| Heater rating | 10 kW |
| Voltage | 480 V |
| Phase | Three phase |
| Heat output | 34,120 BTU/h |
| Current | 12 A |
| Breaker | 20 A |
Mistakes that catch people
- Sizing the circuit at 100% of the heater current.
- Comparing electric and gas on BTU without comparing the fuel cost per million BTU.
- Forgetting the fan motor in a unit heater's load.
Rules of thumb
- 1 kW = 3,412 BTU/h. 1 ton of cooling is 3.5 kW of heat equivalent.
- 480 V three phase: 1.2 amps per kW. 240 V single phase: 4.2.
- Electric heat at 12 cents: about $35 per million BTU.
When to stop calculating and make a call
- Heaters over 30 kW: subdivided circuits and a panel of their own.
- Hazardous locations: the heater's listing governs.
Questions people ask
- How much electric heat does a dock need?
- Figure the heat loss with the warehouse heater calculator and divide by 3,412 for kW. Electric is the simplest to install and the most expensive to run; gas unit heaters or infrared are usual where gas is available, and electric infrared at the dock doors heats people and floors rather than the air.
Standards and sources
- NEC 2020 424.3(B); 1 kW = 3,412 BTU/h
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.