Electrical · guide
Electricity cost: the guide
Watts times hours is energy, energy times the rate is money, and the rate to use is the one on your bill, not the one in the brochure.
Why this number matters
The operating cost of anything electric is its power draw times the hours it runs times what a kilowatt-hour costs. The nameplate gives the maximum power; most equipment draws less most of the time, so a clamp ammeter or a plug-in meter on the real load gives a better number than the plate. The rate is the blended one: total dollars on the bill divided by total kWh, which includes delivery charges, riders, and taxes, and is what the next kilowatt-hour actually costs you.
Commercial bills also carry a demand charge, so much per kW of the month's peak, which the hours do not capture; a piece of equipment that adds to the peak costs that every month on top of its energy. A compressor that runs at night costs its energy; one that runs at 2 pm costs its energy plus its share of the peak.
The number is the base for every payback on the site: lighting retrofits, variable speed drives, compressed air leaks, destratification fans. Get the rate and the hours right once and the rest follows.
How it is figured
- kWh = watts ÷ 1000 × hours; a year is 52 weeks. From amps: watts = amps × volts (× 1.732 for three phase) × 0.85 power factor.
- Cost uses the blended rate; demand charges on commercial bills are extra and depend on the peak kW, not the hours.
A worked example
A 1,500-watt load for ten hours a day, five days a week, is 3,900 kWh a year; at 12 cents that is $468, or about $39 a month.
The tool's starting values, and what it returns for them:
| Power draw | 1,500 W |
| Or nameplate amps | 0 A |
| Volts (for amps) | 120 V |
| Hours per day | 10 h |
| Days per week | 5 |
| Electricity rate | 0.12 $/kWh |
| Cost per year | 468 $ |
| Energy per year | 3,900 kWh |
| Cost per month | 39 $ |
| kWh per day | 15 |
| Power used | 1,500 W |
Mistakes that catch people
- Using the energy rate from the tariff (8 cents) instead of the blended rate from the bill (13 cents).
- Nameplate watts for a motor that runs half loaded.
- Ignoring the demand charge on equipment that runs during the peak.
Rules of thumb
- 1 kW running 24/7 costs about $1,000 a year at 12 cents.
- A motor's draw is roughly its hp × 0.75 kW at full load, less at part load.
- Commercial average rate in the US runs 11 to 15 cents all-in.
When to stop calculating and make a call
- Demand-based tariffs, time-of-use rates, and ratchets: the utility's rate sheet and a 15-minute interval download decide.
- A process load with a profile: an energy audit with logging.
Questions people ask
- Nameplate watts or measured?
- Nameplate is the maximum; most equipment draws less most of the time. A plug-in meter or a clamp ammeter on the actual load gives the real figure, which is what to use for a payback.
- Where do I find my rate?
- Divide the bill's total by the kWh on it. That blended figure includes delivery, taxes, and demand, and it is what another kWh costs you on average.
Standards and sources
- Arithmetic; U.S. EIA average commercial rate about 13 cents per kWh (2025)
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.