Electrical · guide
VFD fan and pump savings: the guide
A fan or pump throttled by a damper or a valve is wasting the cube of the speed it does not need; a drive gives that back.
Why this number matters
Centrifugal fans and pumps follow the affinity laws: flow goes with speed, pressure with the square, and power with the cube. A fan running at 80% speed moves 80% of the air on about half the power; at 50% speed, an eighth. Most fans and pumps in a plant are sized for the worst day and throttled the rest of the time, and the throttling throws the difference away as pressure drop across a damper or a valve. A variable frequency drive slows the motor instead, and the saving is the cube law minus a few percent of drive losses.
The input that matters is the speed the process really needs, which is usually found by asking how far open the damper or valve sits on a normal day. The hours matter as much: a 25 hp fan running 4,000 hours a year at 80% speed saves about 24,000 kWh, which at 12 cents pays for a drive in a year or two.
The law does not apply to everything. Positive displacement pumps and compressors, conveyors, and other constant-torque loads save in proportion to speed, not its cube, and pumps lifting water against a fixed head save less than the law suggests.
How it is figured
- Affinity laws for centrifugal fans and pumps: flow with speed, pressure with speed squared, power with speed cubed. Power at a reduced speed = full-speed power × (speed ratio)³, plus about 3% drive losses.
- Full-speed power = hp × 0.746 × load ÷ motor efficiency. Savings = (full − reduced) kW × hours × rate.
A worked example
A 25 hp fan motor at 85% load draws about 17 kW at full speed. At 80% speed the cube law gives 9 kW, 47% less, which over 4,000 hours saves about 32,000 kWh and $3,800 a year at 12 cents.
The tool's starting values, and what it returns for them:
| Motor horsepower | 25 hp |
| Motor load at full speed | 85 % |
| Speed the process needs | 80 % |
| Run hours per year | 4,000 h |
| Electricity rate | 0.12 $/kWh |
| Motor efficiency | 0.93 |
| Saved per year | 3,863 $ |
| Energy saved per year | 32,194 kWh |
| Power reduction | 47 % |
| Power at full speed | 17 kW |
| Power at reduced speed on the drive | 9 kW |
| kWh per year at full speed | 68,183 |
Mistakes that catch people
- Applying the cube law to a screw compressor or a conveyor.
- Assuming full-speed hours when the fan already cycles off half the time.
- Forgetting the drive needs a bypass and a cooling plan in a hot mechanical room.
Rules of thumb
- 80% speed: half the power. 70%: a third. 50%: an eighth.
- Drive losses about 3%; the motor should be inverter-duty or derated.
- A damper more than 30% closed on a normal day is a drive opportunity.
When to stop calculating and make a call
- Pumps with high static head: the system curve, not the affinity law, sets the saving.
- Older motors: the drive's output can damage non-inverter-duty insulation; the motor shop knows.
Questions people ask
- Why is the saving so large?
- The cube law. A fan at 80% speed draws about half the power; at 50% speed, an eighth. Any fan or pump that is throttled by a damper or a valve is wasting the difference.
- Where does the cube law not apply?
- Positive-displacement pumps and compressors, conveyors, and anything with a constant torque load save roughly in proportion to speed, not its cube. Systems with a lot of static head (a pump lifting water to a height) also save less.
Standards and sources
- ASHRAE Handbook, HVAC Systems and Equipment, fans (affinity laws)
- U.S. DOE, Adjustable Speed Drive Part-Load Efficiency (Motor Systems Tip Sheet)
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.