Motor speed: Hz and poles: the guide
An AC motor's speed is set by the line frequency and its poles, which is why equipment built for 60 Hz runs a sixth slower on 50 Hz and why the plate says 1,750 instead of 1,800.
Why this number matters
An induction motor's rotating magnetic field turns at 120 times the frequency divided by the number of poles: 1,800 rpm for a four-pole motor on 60 Hz, 1,500 on 50 Hz. The rotor has to turn a little slower than the field to make torque, which is the slip, two to four percent at full load, so the nameplate reads 1,750 or 1,765. Two-pole motors run near 3,600 and 3,000; six-pole near 1,200 and 1,000.
Moving a machine between 50 and 60 Hz countries changes everything on the shaft. The motor itself is usually fine at the right voltage: the iron saturates on volts per hertz, so a 460-volt 60 Hz motor wants about 380 volts at 50 Hz, which is the European supply, and it loses a sixth of its horsepower. The driven load is the real question. A fan or pump at five-sixths speed moves five-sixths the flow and draws about 58% of the power, which is harmless; a conveyor runs slow; a compressor delivers less. In the other direction, a 50 Hz machine on 60 Hz runs 20% fast and a fan on it draws 73% more power and overloads its motor.
A variable frequency drive makes the question go away by producing whatever frequency the machine wants from whatever supply exists, which is why imported equipment usually arrives with one.
How it is figured
- Synchronous speed = 120 × frequency ÷ poles. An induction motor runs below that by its slip, 2 to 4% at full load.
- Speed scales with frequency, so a 60 Hz motor on 50 Hz runs at 5/6 speed. At constant voltage the volts-per-hertz ratio rises by 20%, which is why 50 Hz operation calls for lower voltage (380 to 400 V in place of 460) or a derate.
- Centrifugal fans and pumps follow the affinity laws: flow with speed, pressure with speed squared, power with speed cubed.
A worked example
A four-pole motor on 60 Hz has a synchronous speed of 1,800 rpm and runs at 1,746 with 3% slip; on 50 Hz the same motor runs at 1,455, 17% slower, and a fan on it moves 17% less air on 58% of the power.
The tool's starting values, and what it returns for them:
| Line frequency | 60 Hz (North America) |
| Motor poles | 4 poles (1,800 rpm class) |
| Full-load slip | 3 % |
| Motor was built for | 60 Hz |
| Full-load speed | 1,746 rpm |
| Synchronous speed | 1,800 rpm |
| Speed vs design | 100 % |
| Fan or pump power at that speed (cube law) | 100 % of design |
How to read the nameplate
- Find RPM on the nameplate; 1,750 or 1,765 means a 4-pole 60 Hz motor (1,800 synchronous), 3,450 a 2-pole, 1,150 a 6-pole.
- Find Hz and the voltage(s); a dual-rated plate lists both 50 and 60 Hz with different voltages and horsepower.
- Slip = (synchronous − nameplate rpm) ÷ synchronous; enter it for an exact full-load speed.
Tools: the motor nameplate, a flashlight
Mistakes that catch people
- Running a 60 Hz motor on 50 Hz at the 60 Hz voltage; the volts-per-hertz ratio climbs 20% and the windings cook.
- Putting a 50 Hz fan on 60 Hz and wondering why the motor trips: the cube law.
- Reading the nameplate rpm as the synchronous speed.
Rules of thumb
- Speed = 120 × Hz ÷ poles. Four poles: 1,800 at 60 Hz, 1,500 at 50.
- Slip 2 to 4%; nameplate 1,750 means four-pole 60 Hz.
- Fans and pumps: flow with speed, pressure with speed squared, power with speed cubed.
When to stop calculating and make a call
- Dual-rated or inverter-duty motors: the nameplate lists both frequencies and the maker's limits.
- Timers, transformers, and solenoids built for one frequency: the maker says whether they tolerate the other.
Questions people ask
- Can I run a 60 Hz machine in a 50 Hz country?
- An induction motor will run, 17% slower, and it needs about 17% less voltage to stay cool, which 380 to 400 V supplies against a 460 V plate happen to provide. The driven machine is the real question: a fan or pump delivers 17% less and a compressor or conveyor runs 17% slower. Anything with a transformer, a timer, or an electronic drive needs its own check. A VFD solves most of it by making 60 Hz from the 50 Hz supply.
- What is Hz, in plain terms?
- How many times a second the alternating current reverses. North America uses 60, most of the world 50. Motor speed, transformer design, and clock-type timers all depend on it; most electronics do not care.
- Why is my motor nameplate 1,750 and not 1,800?
- Slip. An induction motor has to turn a little slower than the rotating field to produce torque; the gap is the slip, about 3% at full load and nearly zero with no load.
Standards and sources
- NEMA MG 1, Motors and Generators (speed, voltage and frequency variation, sections 12 and 14)
- Affinity laws for centrifugal fans and pumps (ASHRAE Handbook, HVAC Systems and Equipment)
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.