Motor speed from frequency and poles, 50 Hz vs 60 Hz
Line frequency, pole count, and slip in; the synchronous and full-load rpm, and what changes when a 60 Hz machine runs on 50 Hz or the other way around.
Read the guide: what the number means and how to use it
- Synchronous speed = 120 × frequency ÷ poles. An induction motor runs below that by its slip, 2 to 4% at full load.
- Speed scales with frequency, so a 60 Hz motor on 50 Hz runs at 5/6 speed. At constant voltage the volts-per-hertz ratio rises by 20%, which is why 50 Hz operation calls for lower voltage (380 to 400 V in place of 460) or a derate.
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quoteMotor speed: Hz and poles
Full-load speed
1,746 rpm
running at its design frequency
Synchronous speed
1,800 rpm
120 × 60 ÷ 4
Speed vs design
100 %
- Fan or pump power at that speed (cube law)
- 100 % of design
One line for the file or the vendor
4-pole motor on 60 Hz: synchronous 1800 rpm, 1746 rpm at 3% slip; running at its design frequency.
How it is figured
- Synchronous speed = 120 × frequency ÷ poles. An induction motor runs below that by its slip, 2 to 4% at full load.
- Speed scales with frequency, so a 60 Hz motor on 50 Hz runs at 5/6 speed. At constant voltage the volts-per-hertz ratio rises by 20%, which is why 50 Hz operation calls for lower voltage (380 to 400 V in place of 460) or a derate.
- Centrifugal fans and pumps follow the affinity laws: flow with speed, pressure with speed squared, power with speed cubed.
How to read the nameplate
- 1. Find RPM on the nameplate; 1,750 or 1,765 means a 4-pole 60 Hz motor (1,800 synchronous), 3,450 a 2-pole, 1,150 a 6-pole.
- 2. Find Hz and the voltage(s); a dual-rated plate lists both 50 and 60 Hz with different voltages and horsepower.
- 3. Slip = (synchronous − nameplate rpm) ÷ synchronous; enter it for an exact full-load speed.
Tools: the motor nameplate, a flashlight
Sources: NEMA MG 1, Motors and Generators (speed, voltage and frequency variation, sections 12 and 14); Affinity laws for centrifugal fans and pumps (ASHRAE Handbook, HVAC Systems and Equipment). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Can I run a 60 Hz machine in a 50 Hz country?
- An induction motor will run, 17% slower, and it needs about 17% less voltage to stay cool, which 380 to 400 V supplies against a 460 V plate happen to provide. The driven machine is the real question: a fan or pump delivers 17% less and a compressor or conveyor runs 17% slower. Anything with a transformer, a timer, or an electronic drive needs its own check. A VFD solves most of it by making 60 Hz from the 50 Hz supply.
- What is Hz, in plain terms?
- How many times a second the alternating current reverses. North America uses 60, most of the world 50. Motor speed, transformer design, and clock-type timers all depend on it; most electronics do not care.
- Why is my motor nameplate 1,750 and not 1,800?
- Slip. An induction motor has to turn a little slower than the rotating field to produce torque; the gap is the slip, about 3% at full load and nearly zero with no load.
Related calculators: Motor FLA, wire, breaker, VFD fan and pump savings, kW, kVA, amps, hp. All calculators.