Electrical
VFD savings on a fan or pump
Motor size, the speed the process actually needs, hours, and the rate in; the power at reduced speed by the cube law, and the kWh and dollars saved per year.
Read the guide: what the number means and how to use it
- Affinity laws for centrifugal fans and pumps: flow with speed, pressure with speed squared, power with speed cubed. Power at a reduced speed = full-speed power × (speed ratio)³, plus about 3% drive losses.
- Full-speed power = hp × 0.746 × load ÷ motor efficiency. Savings = (full − reduced) kW × hours × rate.
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quoteVFD fan and pump savings
Saved per year
3,863 $
Energy saved per year
32,194 kWh
Power reduction
47 %
at 80% speed, cube law
- Power at full speed
- 17 kW
- Power at reduced speed on the drive
- 9 kW
- kWh per year at full speed
- 68,183
One line for the file or the vendor
25 hp at 85% load, 4000 h/yr, $0.12/kWh, run at 80% speed: 17 to 9 kW, saves 32,194 kWh and $3,863 a year.
How it is figured
- Affinity laws for centrifugal fans and pumps: flow with speed, pressure with speed squared, power with speed cubed. Power at a reduced speed = full-speed power × (speed ratio)³, plus about 3% drive losses.
- Full-speed power = hp × 0.746 × load ÷ motor efficiency. Savings = (full − reduced) kW × hours × rate.
Sources: ASHRAE Handbook, HVAC Systems and Equipment, fans (affinity laws); U.S. DOE, Adjustable Speed Drive Part-Load Efficiency (Motor Systems Tip Sheet). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Why is the saving so large?
- The cube law. A fan at 80% speed draws about half the power; at 50% speed, an eighth. Any fan or pump that is throttled by a damper or a valve is wasting the difference.
- Where does the cube law not apply?
- Positive-displacement pumps and compressors, conveyors, and anything with a constant torque load save roughly in proportion to speed, not its cube. Systems with a lot of static head (a pump lifting water to a height) also save less.