Line Item SupplyIndustrial Equipment
Request a Quote

Electrical

VFD savings on a fan or pump

Motor size, the speed the process actually needs, hours, and the rate in; the power at reduced speed by the cube law, and the kWh and dollars saved per year.

Read the guide: what the number means and how to use it

  • Affinity laws for centrifugal fans and pumps: flow with speed, pressure with speed squared, power with speed cubed. Power at a reduced speed = full-speed power × (speed ratio)³, plus about 3% drive losses.
  • Full-speed power = hp × 0.746 × load ÷ motor efficiency. Savings = (full − reduced) kW × hours × rate.

Need it quoted?

Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.

Request a quote

VFD fan and pump savings

06818368,183 kWh · $3,863

Saved per year

3,863 $

Energy saved per year

32,194 kWh

Power reduction

47 %

at 80% speed, cube law

Power at full speed
17 kW
Power at reduced speed on the drive
9 kW
kWh per year at full speed
68,183

One line for the file or the vendor

25 hp at 85% load, 4000 h/yr, $0.12/kWh, run at 80% speed: 17 to 9 kW, saves 32,194 kWh and $3,863 a year.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Affinity laws for centrifugal fans and pumps: flow with speed, pressure with speed squared, power with speed cubed. Power at a reduced speed = full-speed power × (speed ratio)³, plus about 3% drive losses.
  • Full-speed power = hp × 0.746 × load ÷ motor efficiency. Savings = (full − reduced) kW × hours × rate.

Sources: ASHRAE Handbook, HVAC Systems and Equipment, fans (affinity laws); U.S. DOE, Adjustable Speed Drive Part-Load Efficiency (Motor Systems Tip Sheet). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Why is the saving so large?
The cube law. A fan at 80% speed draws about half the power; at 50% speed, an eighth. Any fan or pump that is throttled by a damper or a valve is wasting the difference.
Where does the cube law not apply?
Positive-displacement pumps and compressors, conveyors, and anything with a constant torque load save roughly in proportion to speed, not its cube. Systems with a lot of static head (a pump lifting water to a height) also save less.

Related calculators: Motor speed: Hz and poles, Electricity cost, HVLS fan sizing. All calculators.