kW, kVA, amps, and horsepower converter
Enter the one you know, kW, kVA, amps, or hp, with the voltage, phase, power factor, and efficiency; get the other three.
Read the guide: what the number means and how to use it
- kW = kVA × power factor. Amps = kVA × 1000 ÷ volts (single phase) or ÷ (volts × 1.732) (three phase).
- Horsepower output = kW input × efficiency ÷ 0.746. kVAR = square root of (kVA² − kW²). One kW is 3,412 BTU/h of heat.
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quotekW, kVA, amps, hp
Real power
50 kW
Apparent power
58.82 kVA
Current
70.8 A
per phase, three phase at 480 V
- Motor output at this input
- 61.7 hp
- Reactive power
- 30.99 kVAR
- Heat equivalent
- 170,600 BTU/h
One line for the file or the vendor
50 kW = 58.82 kVA = 70.8 A at 480 V 3-phase, PF 0.85; 61.7 hp at 0.92 efficiency.
How it is figured
- kW = kVA × power factor. Amps = kVA × 1000 ÷ volts (single phase) or ÷ (volts × 1.732) (three phase).
- Horsepower output = kW input × efficiency ÷ 0.746. kVAR = square root of (kVA² − kW²). One kW is 3,412 BTU/h of heat.
Sources: Standard AC power relationships; NEMA MG 1 for motor efficiency. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- What is the difference between kW and kVA?
- kVA is what the wires and transformer have to carry; kW is the part that does work. The ratio is the power factor. Motors and transformers draw more kVA than kW; heaters draw the same.
- Which number does the utility bill?
- Energy in kWh, and on commercial accounts a demand charge on the peak kW (sometimes kVA). A low power factor can carry a penalty; see the power factor correction calculator.
Related calculators: Breaker size, Transformer sizing, Power factor correction. All calculators.