Transformer kVA and full-load amps

Connected load, growth, voltages, and phase in; the kVA, the next standard size, and the primary and secondary full-load currents.

Read the guide: what the number means and how to use it

  • kVA needed = kW ÷ power factor × (1 + growth). Standard dry-type sizes from the NEMA / manufacturer lists; the next size at or above the need.
  • Full-load amps = kVA × 1000 ÷ volts (single phase) or ÷ (volts × 1.732) (three phase), on each side.

Need it quoted?

Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.

Request a quote

Transformer sizing

112.5 kVAthree phase, 480 to 208 V480 V primary135.3 A208 V secondary312.3 A

Standard size

113 kVA

88.2 kVA needed with 25% growth

Secondary full-load current

312.3 A

at 208 V

Primary full-load current

135.3 A

at 480 V

Primary breaker, 125% rule
150 A450.3(B), secondary protected
Secondary breaker, 125% rule
350 A
size
three phase, 480 to 208 V

One line for the file or the vendor

60 kW at PF 0.85 + 25%: 112.5 kVA 3-phase 480-208 V, primary 135.3 A, secondary 312.3 A.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • kVA needed = kW ÷ power factor × (1 + growth). Standard dry-type sizes from the NEMA / manufacturer lists; the next size at or above the need.
  • Full-load amps = kVA × 1000 ÷ volts (single phase) or ÷ (volts × 1.732) (three phase), on each side.
  • Overcurrent protection per NEC 450.3(B): primary and secondary at 125% of the full-load current, rounded down to a standard size (the next size up is allowed on the primary where 125% is not standard).

Sources: NEC 2020 450.3(B) and Table 450.3(B); NEMA ST 20 (dry-type transformers, standard kVA ratings). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Why add growth?
A transformer runs for decades and loads only grow; 25% is the usual planning margin, and a transformer loaded to 80% runs cooler and lasts longer.
Does the motor inrush matter?
A large motor starting across the line on a small transformer drags the voltage down. Keep the largest motor's starting kVA under about 2.5 times the transformer rating, or use a soft starter or VFD.

Related calculators: kW, kVA, amps, hp, Generator sizing, Breaker size. All calculators.