Electrical
Transformer kVA and full-load amps
Connected load, growth, voltages, and phase in; the kVA, the next standard size, and the primary and secondary full-load currents.
Read the guide: what the number means and how to use it
- kVA needed = kW ÷ power factor × (1 + growth). Standard dry-type sizes from the NEMA / manufacturer lists; the next size at or above the need.
- Full-load amps = kVA × 1000 ÷ volts (single phase) or ÷ (volts × 1.732) (three phase), on each side.
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quoteTransformer sizing
Standard size
113 kVA
88.2 kVA needed with 25% growth
Secondary full-load current
312.3 A
at 208 V
Primary full-load current
135.3 A
at 480 V
- Primary breaker, 125% rule
- 150 A450.3(B), secondary protected
- Secondary breaker, 125% rule
- 350 A
- size
- three phase, 480 to 208 V
One line for the file or the vendor
60 kW at PF 0.85 + 25%: 112.5 kVA 3-phase 480-208 V, primary 135.3 A, secondary 312.3 A.
How it is figured
- kVA needed = kW ÷ power factor × (1 + growth). Standard dry-type sizes from the NEMA / manufacturer lists; the next size at or above the need.
- Full-load amps = kVA × 1000 ÷ volts (single phase) or ÷ (volts × 1.732) (three phase), on each side.
- Overcurrent protection per NEC 450.3(B): primary and secondary at 125% of the full-load current, rounded down to a standard size (the next size up is allowed on the primary where 125% is not standard).
Sources: NEC 2020 450.3(B) and Table 450.3(B); NEMA ST 20 (dry-type transformers, standard kVA ratings). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Why add growth?
- A transformer runs for decades and loads only grow; 25% is the usual planning margin, and a transformer loaded to 80% runs cooler and lasts longer.
- Does the motor inrush matter?
- A large motor starting across the line on a small transformer drags the voltage down. Keep the largest motor's starting kVA under about 2.5 times the transformer rating, or use a soft starter or VFD.
Related calculators: kW, kVA, amps, hp, Generator sizing, Breaker size. All calculators.