Electrical · guide
Transformer sizing: the guide
A transformer is sized on kVA with room to grow, and the breakers on each side come from its full-load current, not from the load behind it.
Why this number matters
The transformer has to carry the connected load's apparent power, so the load in kW is divided by the power factor to get kVA and then given a growth allowance, typically 25%, because transformers outlive the equipment they were bought for. The next standard dry-type size is the order: 15, 30, 45, 75, 112.5, 150, 225, 300, 500 kVA for three phase. A transformer at 80% load runs cooler and longer than one at its plate.
The full-load current on each side is the kVA divided by the voltage and 1.732, and the Code protects the transformer at 125% of that current on the primary, with the secondary protected the same way when the primary device is larger. Those breakers are sized from the transformer, which is why a 112.5 kVA unit on a 208-volt secondary gets a 400-amp secondary breaker even if today's load is 200 amps.
Large motors started across the line on a small transformer pull the voltage down for everyone on it; keeping the biggest motor's starting kVA under about two and a half times the transformer rating, or soft-starting it, avoids the flicker.
How it is figured
- kVA needed = kW ÷ power factor × (1 + growth). Standard dry-type sizes from the NEMA / manufacturer lists; the next size at or above the need.
- Full-load amps = kVA × 1000 ÷ volts (single phase) or ÷ (volts × 1.732) (three phase), on each side.
- Overcurrent protection per NEC 450.3(B): primary and secondary at 125% of the full-load current, rounded down to a standard size (the next size up is allowed on the primary where 125% is not standard).
A worked example
A 60 kW load at 0.85 power factor with 25% growth needs 88 kVA; the standard 112.5 kVA three-phase unit stepping 480 to 208 volts draws 135 amps on the primary and delivers 312 amps on the secondary, with 150-amp and 350-amp breakers at the 125% rule rounded down.
The tool's starting values, and what it returns for them:
| Connected load | 60 kW |
| Power factor | 0.85 |
| Growth allowance | 25 % |
| Phase | Three phase |
| Primary voltage | 480 V |
| Secondary voltage | 208 V (120/208 wye) |
| Standard size | 112.5 kVA |
| Secondary full-load current | 312.3 A |
| Primary full-load current | 135.3 A |
| Primary breaker, 125% rule | 150 A |
| Secondary breaker, 125% rule | 350 A |
| size | three phase, 480 to 208 V |
Mistakes that catch people
- Sizing on kW and forgetting the power factor, 15 to 20% short on motor loads.
- No growth allowance; the next machine overloads it.
- Protecting the secondary from the load instead of the transformer.
Rules of thumb
- kVA = kW ÷ PF × 1.25 for growth.
- Standard three-phase dry types: 15, 30, 45, 75, 112.5, 150, 225, 300, 500 kVA.
- Full-load amps: kVA × 1,000 ÷ (volts × 1.732). Protect at 125%.
When to stop calculating and make a call
- Transformers over 150 kVA, or any that feed a service: fault current and coordination studies.
- Harmonic loads (drives, rectifiers): K-rated transformers are a design choice.
Questions people ask
- Why add growth?
- A transformer runs for decades and loads only grow; 25% is the usual planning margin, and a transformer loaded to 80% runs cooler and lasts longer.
- Does the motor inrush matter?
- A large motor starting across the line on a small transformer drags the voltage down. Keep the largest motor's starting kVA under about 2.5 times the transformer rating, or use a soft starter or VFD.
Standards and sources
- NEC 2020 450.3(B) and Table 450.3(B)
- NEMA ST 20 (dry-type transformers, standard kVA ratings)
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.