Electrical · guide
Breaker size: the guide
A breaker protects the wire, not the equipment. Size it from the load current with the continuous-load bump, then pick the next standard rating.
Why this number matters
The breaker's job is to open before the conductor overheats, so it is chosen from the conductor and the load together: load amps, times 125% if the load runs continuously, rounded up to a standard rating from the Code's list of 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 and on. The conductor must be rated at least the breaker, with the small exception that lets the breaker round up when the wire's ampacity lands between sizes.
Equipment that has a nameplate maximum overcurrent device, which includes most HVAC units and listed machines, uses that number instead; motors use the Code's full-load tables and their own 250% rule, and welders and transformers have their own articles. This calculator covers the ordinary case: a heater, a lighting panel, a receptacle load, a piece of equipment with a kW rating.
Converting kW to amps is where errors creep in: the power factor and the phase both change the current for the same kW, and a three-phase 480-volt load draws a quarter of the current of the same kW at single-phase 240.
How it is figured
- Current = watts ÷ (volts × power factor) single phase, or ÷ (volts × 1.732 × power factor) three phase.
- Continuous loads at 125% (NEC 210.20(A)); breaker is the next standard rating in 240.6(A).
- Conductor from Table 310.16 at 75°C; motors, welders, and HVAC with a nameplate maximum overcurrent device follow their own articles instead.
A worked example
A 10 kW load at 480 volts three phase and 0.9 power factor draws 13.4 amps; at 125% that is 16.7, so a 20-amp breaker on 12 AWG copper.
The tool's starting values, and what it returns for them:
| Load | 10 kW |
| Or nameplate current | 0 A |
| Voltage | 480 V |
| Phase | Three phase |
| Power factor | 0.9 |
| Continuous load | Yes, 3 hours or more |
| Breaker | 20 A |
| Load current | 13.4 A |
| Design current | 16.7 A |
| Copper conductor at 75°C | 14 AWG |
Mistakes that catch people
- Oversizing the breaker to stop nuisance trips; the wire is then unprotected.
- Forgetting the power factor on motor loads and under-sizing the current.
- Using the breaker to size the wire instead of the other way round.
Rules of thumb
- Standard breaker sizes step by 5 to 50 amps, by 10 to 100, then 110, 125, 150, 175, 200, 225, 250.
- Continuous: 125%. Nameplate maximum overcurrent device: use it.
- kW ÷ (volts × 1.732 × PF) = three-phase amps.
When to stop calculating and make a call
- Adding a breaker to a panel at its capacity: load calculations and panel ratings are an electrician's call.
- Anything with a listed maximum fuse or breaker on the nameplate.
Questions people ask
- What if the nameplate gives a maximum breaker?
- Use it. Air conditioners, heat pumps, and listed equipment often carry a maximum overcurrent protection figure, and the nameplate governs over the generic 125% rule.
- Motors?
- Motors are sized from the NEC full-load current tables, not the nameplate, with conductors at 125% and an inverse-time breaker allowed up to 250%; use the motor calculator.
Standards and sources
- NEC 2020 210.20(A), 240.6(A), Table 310.16
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.