Electrical · guide
Motor FLA, wire, breaker: the guide
Motors are sized by the Code's table current, not the nameplate, with the wire at 125% and a breaker allowed up to 250% so the inrush does not trip it.
Why this number matters
Article 430 of the National Electrical Code treats motors differently because they draw five to eight times their running current for a second when they start. The conductor is sized at 125% of the full-load current from the Code's tables, so that any replacement motor of the same horsepower fits the circuit. The short-circuit protection, an inverse-time breaker, may be as large as 250% of that current, which would never protect the wire against overload; the overload relay in the starter does that, set from the nameplate current of the motor actually installed.
The three numbers come apart on purpose: table current for the wire and the breaker, nameplate current for the overloads. On a 20-horsepower 460-volt motor that is 27 amps from the table, a 34-amp conductor (8 AWG copper at 75°C), and a breaker up to 60 amps, with overloads set from the plate, around 26 to 30 amps depending on the service factor.
The tables cover standard 60 Hz voltages from 1/2 to 500 horsepower. For 50 Hz motors or odd voltages the nameplate current at 125% sizes the conductor and the same breaker percentages apply.
How it is figured
- Full-load current from NEC Table 430.250 (three phase) or 430.248 (single phase), which the Code requires for sizing conductors and short-circuit protection instead of the nameplate.
- Branch conductors at 125% of the table current (430.22); conductor from Table 310.16 at 75°C.
- Inverse-time breaker up to 250% of the table current (Table 430.52), rounded down to a standard size; 430.52(C)(1) Exception 1 allows the next size up when a standard size does not fit. Overloads are set from the nameplate current (430.32).
A worked example
A 20 hp three-phase 460-volt motor: 27 amps from Table 430.250, conductor at 125% is 33.8 amps so 8 AWG copper, inverse-time breaker up to 67.5 amps rounded down to 60, overloads set at 125% of the nameplate current.
The tool's starting values, and what it returns for them:
| Motor horsepower | 20 hp |
| Phase | Three phase |
| Voltage | 460 V |
| Conductor | Copper |
| Full-load current (NEC table) | 27 A |
| Branch conductor at 125% | 33.8 A |
| Largest inverse-time breaker | 60 A |
| Overload setting, service factor 1.15 | 33.8 A |
Mistakes that catch people
- Sizing the overload relay from the table current; it must come from the nameplate.
- A 20-amp breaker on a 15 hp motor because the wire is 10 AWG: the motor will not start.
- Forgetting the disconnect within sight of the motor.
Rules of thumb
- 460 V three phase: about 1.25 amps per hp. 230 V: 2.5. 208 V: 2.8.
- Conductor 125%, inverse-time breaker up to 250%, overloads from the nameplate.
- Multiple motors on one feeder: 125% of the largest plus the sum of the rest.
When to stop calculating and make a call
- Motor control centers, soft starters, and VFDs: the drive manufacturer's instructions govern the input protection.
- Any motor over 100 hp: starting method and utility coordination come first.
Questions people ask
- Why not use the nameplate amps?
- The NEC says the table current sizes the wire and the breaker so that any replacement motor of the same horsepower fits the circuit; the nameplate current sets the overload relay, which protects that specific motor.
- Can the breaker really be 250%?
- Up to 250% for an inverse-time breaker because the motor's inrush would trip a breaker sized to the running current. The conductors are protected by the overload relay, not the breaker, which is why the two are sized differently.
- What about 50 Hz motors or 380 V?
- The tables are 60 Hz North American voltages. For other voltages use the nameplate current at 125% for conductors and the same 250% breaker rule.
Standards and sources
- NEC 2020 Tables 430.248 and 430.250, 430.22, 430.32, Table 430.52
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.