Voltage drop: the guide

Wire has resistance, so the voltage at the far end of a long run is lower than at the panel. Three percent is the line most designs hold, and the wire size is what holds it.

Open the calculator

Why this number matters

Every foot of conductor drops a little voltage in proportion to the current through it. On a short branch circuit it does not matter; on a 250-foot run to a dock leveler motor or a 400-foot feeder to a remote panel it does. Motors run hot and lose torque on low voltage, lights dim, electronics reset, and the losses show up as heat in the wire and on the bill. The National Electrical Code recommends, in an informational note, no more than 3% on a branch circuit or feeder and 5% in total from the service to the farthest outlet, and most specifications make that a requirement.

The calculation is a resistance formula with the conductor's circular mils and a constant for copper or aluminum, doubled for single phase because the current goes out and back, times 1.732 for three phase. It is the length one way that goes in. Upsizing the wire is the fix: each AWG step is about 26% more circular mils, and going from 6 to 4 AWG on a long run is often the difference between a motor that starts and one that trips.

Voltage drop is only one of two checks. The conductor also has to carry the current at its temperature rating, with continuous loads at 125%, and the calculator flags a wire that fails ampacity first.

How it is figured

  • Single phase: drop = 2 × K × I × L ÷ circular mils. Three phase: drop = 1.732 × K × I × L ÷ circular mils. K is 12.9 ohm-cmil/ft for copper and 21.2 for aluminum at 75°C; L is the one-way length in feet.
  • Circular mils from NEC Chapter 9 Table 8; ampacity from Table 310.16 at the 75°C column, the usual termination rating.
  • The NEC recommends (Informational Note to 210.19 and 215.2) no more than 3% on a branch circuit or feeder and 5% total; the smallest wire shown is the one whose circular mils keep the drop at 3%.

A worked example

A 60-amp three-phase load 250 feet from a 480-volt panel on 4 AWG copper drops 8 volts, 1.67%, and sees 472 volts; the same load on 6 AWG would drop 12.7 volts, 2.6%, still inside 3%, so 6 AWG is the smallest wire that holds the line.

The tool's starting values, and what it returns for them:

System voltage480 V
PhaseThree phase
ConductorCopper
Wire size4 AWG
Load current60 A
One-way length250 ft
Voltage drop8 V
Percent1.67 %
Voltage at the load472 V
Smallest wire that holds 3%6 AWG
Ampacity of 4 AWG at 75°C85 A

How to get the numbers

  1. Read the load's nameplate amps, or the breaker size if the load is not known, and the voltage and phase from the panel schedule.
  2. Measure the conduit route from the panel to the load with a wheel, adding the vertical runs; it is longer than the floor distance.
  3. Read the conductor size off the wire jacket or the panel schedule, and whether it is copper or aluminum.

Tools: measuring wheel, the panel schedule

Mistakes that catch people

  • Measuring the run as the crow flies; the conduit goes up the wall, across the joists, and down, and that is the length.
  • Using the round-trip length in the single-phase formula, which already doubles it.
  • Holding 3% on the branch and forgetting the feeder ahead of it already took 2.5%.

Rules of thumb

  • 12 AWG copper carries 20 amps about 50 feet at 120 volts before it passes 3%.
  • Each wire size up is about 26% less drop; two sizes about 60%.
  • Doubling the voltage cuts the percent drop by four for the same power.

When to stop calculating and make a call

  • Feeders over 200 amps or parallel conductors: an electrical engineer sizes them with the fault current.
  • A motor that will not start on a long run: the starting current, six times running, is what to check.

Questions people ask

Is 3% a code requirement?
In the NEC it is an Informational Note, a recommendation, except where energy codes or 647.4(D) sensitive equipment rules make it mandatory. Most specifications and utilities treat 3% on a feeder or branch and 5% overall as the design limit, and motors and electronics run better for it.
Why does length count one way?
The formula already doubles it: a single-phase circuit's current goes out on one wire and back on the other, which is the 2 in the equation, and the 1.732 does the same for three phase.
What about the ampacity table?
Voltage drop is only half the check. The conductor also has to carry the load at its temperature rating, and continuous loads are sized at 125%; the calculator flags a wire that fails ampacity before it fails voltage drop.

Standards and sources

  • NEC 2020, Chapter 9 Table 8 (conductor properties) and Table 310.16 (ampacities)
  • NEC 210.19(A) and 215.2(A) Informational Notes (3% and 5% voltage drop)

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.