Electrical
Voltage drop on a feeder or branch circuit
Wire size, length, load, and voltage in; the drop in volts and percent, the voltage at the load, and the smallest wire that holds 3%.
Read the guide: what the number means and how to use it
- Single phase: drop = 2 × K × I × L ÷ circular mils. Three phase: drop = 1.732 × K × I × L ÷ circular mils. K is 12.9 ohm-cmil/ft for copper and 21.2 for aluminum at 75°C; L is the one-way length in feet.
- Circular mils from NEC Chapter 9 Table 8; ampacity from Table 310.16 at the 75°C column, the usual termination rating.
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quoteVoltage drop
Voltage drop
8 V
Percent
1.67 %
within 3%
Voltage at the load
472 V
- Smallest wire that holds 3%
- 6 AWGcopper at 60 A over 250 ft
- Ampacity of 4 AWG at 75°C
- 85 A
One line for the file or the vendor
3-phase 480 V, 60 A, 250 ft one way, 4 AWG Cu: drop 8 V (1.67%), 472 V at the load; 6 AWG holds 3%.
How it is figured
- Single phase: drop = 2 × K × I × L ÷ circular mils. Three phase: drop = 1.732 × K × I × L ÷ circular mils. K is 12.9 ohm-cmil/ft for copper and 21.2 for aluminum at 75°C; L is the one-way length in feet.
- Circular mils from NEC Chapter 9 Table 8; ampacity from Table 310.16 at the 75°C column, the usual termination rating.
- The NEC recommends (Informational Note to 210.19 and 215.2) no more than 3% on a branch circuit or feeder and 5% total; the smallest wire shown is the one whose circular mils keep the drop at 3%.
How to get the numbers
- 1. Read the load's nameplate amps, or the breaker size if the load is not known, and the voltage and phase from the panel schedule.
- 2. Measure the conduit route from the panel to the load with a wheel, adding the vertical runs; it is longer than the floor distance.
- 3. Read the conductor size off the wire jacket or the panel schedule, and whether it is copper or aluminum.
Tools: measuring wheel, the panel schedule
Sources: NEC 2020, Chapter 9 Table 8 (conductor properties) and Table 310.16 (ampacities); NEC 210.19(A) and 215.2(A) Informational Notes (3% and 5% voltage drop). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Is 3% a code requirement?
- In the NEC it is an Informational Note, a recommendation, except where energy codes or 647.4(D) sensitive equipment rules make it mandatory. Most specifications and utilities treat 3% on a feeder or branch and 5% overall as the design limit, and motors and electronics run better for it.
- Why does length count one way?
- The formula already doubles it: a single-phase circuit's current goes out on one wire and back on the other, which is the 2 in the equation, and the 1.732 does the same for three phase.
- What about the ampacity table?
- Voltage drop is only half the check. The conductor also has to carry the load at its temperature rating, and continuous loads are sized at 125%; the calculator flags a wire that fails ampacity before it fails voltage drop.
Related calculators: Wire size for amps, Breaker size, Motor FLA, wire, breaker. All calculators.