Voltage drop on a feeder or branch circuit

Wire size, length, load, and voltage in; the drop in volts and percent, the voltage at the load, and the smallest wire that holds 3%.

Read the guide: what the number means and how to use it

  • Single phase: drop = 2 × K × I × L ÷ circular mils. Three phase: drop = 1.732 × K × I × L ÷ circular mils. K is 12.9 ohm-cmil/ft for copper and 21.2 for aluminum at 75°C; L is the one-way length in feet.
  • Circular mils from NEC Chapter 9 Table 8; ampacity from Table 310.16 at the 75°C column, the usual termination rating.

Need it quoted?

Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.

Request a quote

Voltage drop

PANEL480 V250 ft one way · 60 ALOAD472.0 V8.0 V drop, 1.67%within the 3% branch circuit recommendation

Voltage drop

8 V

Percent

1.67 %

within 3%

Voltage at the load

472 V

Smallest wire that holds 3%
6 AWGcopper at 60 A over 250 ft
Ampacity of 4 AWG at 75°C
85 A

One line for the file or the vendor

3-phase 480 V, 60 A, 250 ft one way, 4 AWG Cu: drop 8 V (1.67%), 472 V at the load; 6 AWG holds 3%.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Single phase: drop = 2 × K × I × L ÷ circular mils. Three phase: drop = 1.732 × K × I × L ÷ circular mils. K is 12.9 ohm-cmil/ft for copper and 21.2 for aluminum at 75°C; L is the one-way length in feet.
  • Circular mils from NEC Chapter 9 Table 8; ampacity from Table 310.16 at the 75°C column, the usual termination rating.
  • The NEC recommends (Informational Note to 210.19 and 215.2) no more than 3% on a branch circuit or feeder and 5% total; the smallest wire shown is the one whose circular mils keep the drop at 3%.

How to get the numbers

  1. 1. Read the load's nameplate amps, or the breaker size if the load is not known, and the voltage and phase from the panel schedule.
  2. 2. Measure the conduit route from the panel to the load with a wheel, adding the vertical runs; it is longer than the floor distance.
  3. 3. Read the conductor size off the wire jacket or the panel schedule, and whether it is copper or aluminum.

Tools: measuring wheel, the panel schedule

Sources: NEC 2020, Chapter 9 Table 8 (conductor properties) and Table 310.16 (ampacities); NEC 210.19(A) and 215.2(A) Informational Notes (3% and 5% voltage drop). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Is 3% a code requirement?
In the NEC it is an Informational Note, a recommendation, except where energy codes or 647.4(D) sensitive equipment rules make it mandatory. Most specifications and utilities treat 3% on a feeder or branch and 5% overall as the design limit, and motors and electronics run better for it.
Why does length count one way?
The formula already doubles it: a single-phase circuit's current goes out on one wire and back on the other, which is the 2 in the equation, and the 1.732 does the same for three phase.
What about the ampacity table?
Voltage drop is only half the check. The conductor also has to carry the load at its temperature rating, and continuous loads are sized at 125%; the calculator flags a wire that fails ampacity before it fails voltage drop.

Related calculators: Wire size for amps, Breaker size, Motor FLA, wire, breaker. All calculators.