What wire size for this many amps
Load amps, continuous or not, copper or aluminum in; the smallest conductor from the NEC 75°C table and the breaker that goes with it.
Read the guide: what the number means and how to use it
- Continuous loads are sized at 125% (NEC 210.19(A)(1), 215.2(A)(1)); the conductor is the smallest in Table 310.16 at the 75°C column whose ampacity meets that figure.
- The breaker is the next standard size from 240.6(A) at or above the design current; 240.4(B) allows the next size up when the conductor ampacity falls between sizes, up to 800 A.
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quoteWire size for amps
Smallest conductor, 75°C
6 AWG
copper, rated 65 A
Design current
60 A
125% of the continuous load
Breaker
60 A
next standard size at or above the design current
- Voltage drop at 480 V 3-phase over this length
- 0.85 %
One line for the file or the vendor
48 A continuous load, Cu: design 60 A, 6 AWG at 75°C, 60 A breaker.
How it is figured
- Continuous loads are sized at 125% (NEC 210.19(A)(1), 215.2(A)(1)); the conductor is the smallest in Table 310.16 at the 75°C column whose ampacity meets that figure.
- The breaker is the next standard size from 240.6(A) at or above the design current; 240.4(B) allows the next size up when the conductor ampacity falls between sizes, up to 800 A.
- Small conductors keep their own limits: 14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A (240.4(D)), and the table already reflects them.
Sources: NEC 2020 Table 310.16, 210.19, 215.2, 240.4, 240.6. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Why 75°C and not 90°C?
- Most breaker and equipment terminals are rated 75°C, so the conductor is used at the 75°C ampacity even when its insulation (THHN) is 90°C. The 90°C column is used only for derating adjustments.
- When is a load continuous?
- When it is expected to run for three hours or more: lighting, HVAC, process equipment, EV chargers, dock equipment on a shift. Motors have their own rule, 125% of the table full-load current, in Article 430.
- Does this cover derating?
- No. More than three current-carrying conductors in a raceway and high ambient temperatures reduce the ampacity (310.15); the voltage drop calculator covers the long-run check.
Related calculators: Voltage drop, Breaker size, Motor FLA, wire, breaker. All calculators.