What wire size for this many amps

Load amps, continuous or not, copper or aluminum in; the smallest conductor from the NEC 75°C table and the breaker that goes with it.

Read the guide: what the number means and how to use it

  • Continuous loads are sized at 125% (NEC 210.19(A)(1), 215.2(A)(1)); the conductor is the smallest in Table 310.16 at the 75°C column whose ampacity meets that figure.
  • The breaker is the next standard size from 240.6(A) at or above the design current; 240.4(B) allows the next size up when the conductor ampacity falls between sizes, up to 800 A.

Need it quoted?

Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.

Request a quote

Wire size for amps

design amps60 Abreaker60 A

Smallest conductor, 75°C

6 AWG

copper, rated 65 A

Design current

60 A

125% of the continuous load

Breaker

60 A

next standard size at or above the design current

Voltage drop at 480 V 3-phase over this length
0.85 %

One line for the file or the vendor

48 A continuous load, Cu: design 60 A, 6 AWG at 75°C, 60 A breaker.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Continuous loads are sized at 125% (NEC 210.19(A)(1), 215.2(A)(1)); the conductor is the smallest in Table 310.16 at the 75°C column whose ampacity meets that figure.
  • The breaker is the next standard size from 240.6(A) at or above the design current; 240.4(B) allows the next size up when the conductor ampacity falls between sizes, up to 800 A.
  • Small conductors keep their own limits: 14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A (240.4(D)), and the table already reflects them.

Sources: NEC 2020 Table 310.16, 210.19, 215.2, 240.4, 240.6. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Why 75°C and not 90°C?
Most breaker and equipment terminals are rated 75°C, so the conductor is used at the 75°C ampacity even when its insulation (THHN) is 90°C. The 90°C column is used only for derating adjustments.
When is a load continuous?
When it is expected to run for three hours or more: lighting, HVAC, process equipment, EV chargers, dock equipment on a shift. Motors have their own rule, 125% of the table full-load current, in Article 430.
Does this cover derating?
No. More than three current-carrying conductors in a raceway and high ambient temperatures reduce the ampacity (310.15); the voltage drop calculator covers the long-run check.

Related calculators: Voltage drop, Breaker size, Motor FLA, wire, breaker. All calculators.