Horsepower, voltage, and phase in; the NEC table full-load current, the conductor at 125%, and the largest inverse-time breaker the Code allows.
Read the guide: what the number means and how to use it
- Full-load current from NEC Table 430.250 (three phase) or 430.248 (single phase), which the Code requires for sizing conductors and short-circuit protection instead of the nameplate.
- Branch conductors at 125% of the table current (430.22); conductor from Table 310.16 at 75°C.
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quoteMotor FLA, wire, breaker
Full-load current (NEC table)
27 A
Branch conductor at 125%
33.8 A
10 AWG Cu at 75°C
Largest inverse-time breaker
60 A
250% of the table current, rounded down to a standard size
- Overload setting, service factor 1.15
- 33.8 Afrom the nameplate current, not the table
One line for the file or the vendor
20 hp 3-phase 460 V: FLA 27 A (NEC table), conductor 33.8 A min (10 AWG Cu), inverse-time breaker up to 60 A.
How it is figured
- Full-load current from NEC Table 430.250 (three phase) or 430.248 (single phase), which the Code requires for sizing conductors and short-circuit protection instead of the nameplate.
- Branch conductors at 125% of the table current (430.22); conductor from Table 310.16 at 75°C.
- Inverse-time breaker up to 250% of the table current (Table 430.52), rounded down to a standard size; 430.52(C)(1) Exception 1 allows the next size up when a standard size does not fit. Overloads are set from the nameplate current (430.32).
Sources: NEC 2020 Tables 430.248 and 430.250, 430.22, 430.32, Table 430.52. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Why not use the nameplate amps?
- The NEC says the table current sizes the wire and the breaker so that any replacement motor of the same horsepower fits the circuit; the nameplate current sets the overload relay, which protects that specific motor.
- Can the breaker really be 250%?
- Up to 250% for an inverse-time breaker because the motor's inrush would trip a breaker sized to the running current. The conductors are protected by the overload relay, not the breaker, which is why the two are sized differently.
- What about 50 Hz motors or 380 V?
- The tables are 60 Hz North American voltages. For other voltages use the nameplate current at 125% for conductors and the same 250% breaker rule.
Related calculators: Voltage drop, Wire size for amps, Motor speed: Hz and poles. All calculators.