Motor full-load amps, wire, and breaker

Horsepower, voltage, and phase in; the NEC table full-load current, the conductor at 125%, and the largest inverse-time breaker the Code allows.

Read the guide: what the number means and how to use it

  • Full-load current from NEC Table 430.250 (three phase) or 430.248 (single phase), which the Code requires for sizing conductors and short-circuit protection instead of the nameplate.
  • Branch conductors at 125% of the table current (430.22); conductor from Table 310.16 at 75°C.

Need it quoted?

Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.

Request a quote

Motor FLA, wire, breaker

FLA27 Aconductor33.8 Abreaker max60 A

Full-load current (NEC table)

27 A

Branch conductor at 125%

33.8 A

10 AWG Cu at 75°C

Largest inverse-time breaker

60 A

250% of the table current, rounded down to a standard size

Overload setting, service factor 1.15
33.8 Afrom the nameplate current, not the table

One line for the file or the vendor

20 hp 3-phase 460 V: FLA 27 A (NEC table), conductor 33.8 A min (10 AWG Cu), inverse-time breaker up to 60 A.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Full-load current from NEC Table 430.250 (three phase) or 430.248 (single phase), which the Code requires for sizing conductors and short-circuit protection instead of the nameplate.
  • Branch conductors at 125% of the table current (430.22); conductor from Table 310.16 at 75°C.
  • Inverse-time breaker up to 250% of the table current (Table 430.52), rounded down to a standard size; 430.52(C)(1) Exception 1 allows the next size up when a standard size does not fit. Overloads are set from the nameplate current (430.32).

Sources: NEC 2020 Tables 430.248 and 430.250, 430.22, 430.32, Table 430.52. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Why not use the nameplate amps?
The NEC says the table current sizes the wire and the breaker so that any replacement motor of the same horsepower fits the circuit; the nameplate current sets the overload relay, which protects that specific motor.
Can the breaker really be 250%?
Up to 250% for an inverse-time breaker because the motor's inrush would trip a breaker sized to the running current. The conductors are protected by the overload relay, not the breaker, which is why the two are sized differently.
What about 50 Hz motors or 380 V?
The tables are 60 Hz North American voltages. For other voltages use the nameplate current at 125% for conductors and the same 250% breaker rule.

Related calculators: Voltage drop, Wire size for amps, Motor speed: Hz and poles. All calculators.