Electrical
Breaker size for a load
Load in watts or amps, voltage and phase in; the current, the 125% continuous rule, and the standard breaker.
Read the guide: what the number means and how to use it
- Current = watts ÷ (volts × power factor) single phase, or ÷ (volts × 1.732 × power factor) three phase.
- Continuous loads at 125% (NEC 210.20(A)); breaker is the next standard rating in 240.6(A).
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quoteBreaker size
Breaker
20 A
next standard size
Load current
13.4 A
Design current
16.7 A
125% continuous
- Copper conductor at 75°C
- 14 AWG
One line for the file or the vendor
10 kW at 480 V 3-phase, PF 0.9: 13.4 A, design 16.7 A, 20 A breaker, 14 AWG Cu.
How it is figured
- Current = watts ÷ (volts × power factor) single phase, or ÷ (volts × 1.732 × power factor) three phase.
- Continuous loads at 125% (NEC 210.20(A)); breaker is the next standard rating in 240.6(A).
- Conductor from Table 310.16 at 75°C; motors, welders, and HVAC with a nameplate maximum overcurrent device follow their own articles instead.
Sources: NEC 2020 210.20(A), 240.6(A), Table 310.16. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- What if the nameplate gives a maximum breaker?
- Use it. Air conditioners, heat pumps, and listed equipment often carry a maximum overcurrent protection figure, and the nameplate governs over the generic 125% rule.
- Motors?
- Motors are sized from the NEC full-load current tables, not the nameplate, with conductors at 125% and an inverse-time breaker allowed up to 250%; use the motor calculator.
Related calculators: Wire size for amps, Motor FLA, wire, breaker, kW, kVA, amps, hp. All calculators.