Wire size for amps: the guide

The conductor for a load comes from one table, Table 310.16 at the 75°C column, after the load has been bumped 25% if it runs continuously.

Open the calculator

Why this number matters

Conductors are rated for the current they can carry without their insulation overheating, and the National Electrical Code lists those ampacities by wire size, material, and temperature rating. Nearly all breaker and equipment terminals are rated 75°C, so that column is the one in use even with 90°C wire. Loads that run three hours or more, which is most equipment in a plant, are sized at 125% of their current so the conductor is never at its full rating for long.

The breaker then protects that conductor: the next standard size at or above the design current, with the Code allowing the next size up when the ampacity falls between standard ratings. Small conductors have their own hard limits, 15 amps for 14 AWG, 20 for 12, 30 for 10, which the table already reflects.

What the table does not include is the adjustment for more than three current-carrying conductors in a raceway or for hot ambient, which reduces the ampacity, and the voltage drop on a long run, which can require a bigger wire than the ampacity does. The calculator shows the drop at 480 volts three phase so a long run is caught.

How it is figured

  • Continuous loads are sized at 125% (NEC 210.19(A)(1), 215.2(A)(1)); the conductor is the smallest in Table 310.16 at the 75°C column whose ampacity meets that figure.
  • The breaker is the next standard size from 240.6(A) at or above the design current; 240.4(B) allows the next size up when the conductor ampacity falls between sizes, up to 800 A.
  • Small conductors keep their own limits: 14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A (240.4(D)), and the table already reflects them.

A worked example

A 48-amp continuous load is designed at 60 amps; 6 AWG copper is rated 65 amps at 75°C and a 60-amp breaker protects it. Over 100 feet at 480 volts three phase the drop is under 1%.

The tool's starting values, and what it returns for them:

Load current48 A
Continuous loadYes, runs 3 hours or more (lighting, HVAC, most equipment)
ConductorCopper
One-way length100 ft
Smallest conductor, 75°C6 AWG
Design current60 A
Breaker60 A
Voltage drop at 480 V 3-phase over this length0.85 %

Mistakes that catch people

  • Using the 90°C column because the wire is THHN; the terminals are 75°C.
  • Sizing a motor from this table instead of Article 430's full-load currents.
  • Running six conductors in a conduit at the single-circuit ampacity; derating applies.

Rules of thumb

  • Continuous loads: 125%.
  • 12 AWG copper: 20 amps. 10: 30. 8: 50. 6: 65. 4: 85. 2: 115. 1/0: 150. 2/0: 175. 4/0: 230.
  • Aluminum: about one size larger than copper for the same amps.

When to stop calculating and make a call

  • Conductors over 4/0, parallel runs, or anything in a hot or crowded raceway: derating is an engineer's table work.
  • Service and feeder calculations for a building: Article 220 and a licensed design.

Questions people ask

Why 75°C and not 90°C?
Most breaker and equipment terminals are rated 75°C, so the conductor is used at the 75°C ampacity even when its insulation (THHN) is 90°C. The 90°C column is used only for derating adjustments.
When is a load continuous?
When it is expected to run for three hours or more: lighting, HVAC, process equipment, EV chargers, dock equipment on a shift. Motors have their own rule, 125% of the table full-load current, in Article 430.
Does this cover derating?
No. More than three current-carrying conductors in a raceway and high ambient temperatures reduce the ampacity (310.15); the voltage drop calculator covers the long-run check.

Standards and sources

  • NEC 2020 Table 310.16, 210.19, 215.2, 240.4, 240.6

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.