Electrical · guide
kW, kVA, amps, hp: the guide
kW is the work, kVA is what the wires carry, amps is what the breaker sees, and horsepower is what the shaft delivers; the power factor and the efficiency connect them.
Why this number matters
Real power in kilowatts is what turns into heat, light, and motion. Apparent power in kVA is the product of volts and amps the circuit actually carries, and the ratio of the two is the power factor, which is 1.0 for a heater and 0.8 to 0.9 for a loaded motor. Transformers, feeders, and generators are rated in kVA because the current is what heats them; the utility bills kWh for energy and often kVA or kW for demand.
Horsepower is output on the shaft; the electrical input is larger by the motor's efficiency, so a 50 hp motor draws about 40 kW and about 47 kVA. Three-phase current is the kVA divided by the line voltage times the square root of three, which is why 480-volt three-phase equipment draws so much less current than 240-volt single-phase for the same power.
Most sizing mistakes are conversions: a 100 kVA transformer loaded to 100 kW at 0.8 power factor is 25% overloaded, and a generator rated 100 kW at 0.8 is a 125 kVA machine.
How it is figured
- kW = kVA × power factor. Amps = kVA × 1000 ÷ volts (single phase) or ÷ (volts × 1.732) (three phase).
- Horsepower output = kW input × efficiency ÷ 0.746. kVAR = square root of (kVA² − kW²). One kW is 3,412 BTU/h of heat.
A worked example
A 50 kW three-phase load at 480 volts and 0.85 power factor is 58.8 kVA and draws 70.8 amps per phase; the same input would drive a motor delivering about 62 horsepower at 92% efficiency.
The tool's starting values, and what it returns for them:
| What you know | kW (real power) |
| Value | 50 |
| Voltage | 480 V |
| Phase | Three phase |
| Power factor | 0.85 |
| Motor efficiency | 0.92 |
| Real power | 50 kW |
| Apparent power | 58.82 kVA |
| Current | 70.8 A |
| Motor output at this input | 61.7 hp |
| Reactive power | 30.99 kVAR |
| Heat equivalent | 170,600 BTU/h |
Mistakes that catch people
- Treating kW and kVA as the same number on motor loads.
- Converting horsepower at 746 watts without the efficiency, which understates the input 8 to 15%.
- Single-phase arithmetic on three-phase equipment, a factor of 1.732 in the current.
Rules of thumb
- kVA = kW ÷ PF. Amps = kVA × 1,000 ÷ (volts × 1.732) three phase.
- 1 hp = 0.746 kW on the shaft; about 0.85 kW of input at a typical efficiency.
- 480 V three phase: 1.2 amps per kVA. 208 V three phase: 2.8. 240 V single phase: 4.2.
When to stop calculating and make a call
- Demand charges and power factor penalties: the utility's tariff defines which number is billed.
- Harmonics from drives distort the power factor reading; a power quality meter sorts it out.
Questions people ask
- What is the difference between kW and kVA?
- kVA is what the wires and transformer have to carry; kW is the part that does work. The ratio is the power factor. Motors and transformers draw more kVA than kW; heaters draw the same.
- Which number does the utility bill?
- Energy in kWh, and on commercial accounts a demand charge on the peak kW (sometimes kVA). A low power factor can carry a penalty; see the power factor correction calculator.
Standards and sources
- Standard AC power relationships; NEMA MG 1 for motor efficiency
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.