Electrical
Power factor correction capacitors
Load kW, the power factor now, and the target in; the kVAR of capacitors to add, the kVA freed up, and the current reduction.
Read the guide: what the number means and how to use it
- kVAR to add = kW × (tan(arccos PF now) − tan(arccos PF target)).
- kVA = kW ÷ PF on each side; the difference is capacity released in the transformer and feeders, and current falls in the same ratio.
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quotePower factor correction
Capacitors to add
94.7 kVAR
a 100 kVAR bank in 25 kVAR steps
kVA released
45.9 kVA
256 to 211 kVA
Line current reduction
17.9 %
One line for the file or the vendor
200 kW from PF 0.78 to 0.95: add 94.7 kVAR (100 kVAR bank), releases 45.9 kVA, current down 17.9%.
How it is figured
- kVAR to add = kW × (tan(arccos PF now) − tan(arccos PF target)).
- kVA = kW ÷ PF on each side; the difference is capacity released in the transformer and feeders, and current falls in the same ratio.
Sources: IEEE Std 141 (Red Book), power factor improvement; Eaton / Schneider power factor correction application guides. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Is correction worth it?
- When the utility bills a power factor penalty or a kVA demand charge, usually yes, with paybacks of one to three years on a plant full of motors. Without a penalty the gain is transformer and feeder capacity and slightly lower losses.
- Where do the capacitors go?
- Either a switched bank at the service, which fixes the bill, or capacitors at the large motors, which also unload the feeders. Do not fix capacitors on a motor controlled by a VFD or with a soft starter without the manufacturer's say-so.
Related calculators: kW, kVA, amps, hp, Transformer sizing. All calculators.