Electric heater: kW to BTU/h and amps

Heater kW in; the BTU per hour it delivers, the amps it draws at the voltage, the breaker, and the wire.

Read the guide: what the number means and how to use it

  • 1 kW = 3,412 BTU/h; resistance heat converts all of it. Amps = watts ÷ volts (single phase) or ÷ (volts × 1.732) (three phase); power factor 1.0.
  • Fixed electric space heating is a continuous load: conductors and breaker at 125% (NEC 424.3(B)).

Need it quoted?

Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.

Request a quote

Electric heat kW, BTU, amps

34,120 BTU/h · 1 unit heater at 34,120 BTU/h

Heat output

34,120 BTU/h

Current

12 A

3-phase at 480 V

Breaker

20 A

125% continuous, 14 AWG Cu

One line for the file or the vendor

10 kW heater at 480 V 3-phase: 34,120 BTU/h, 12 A, 20 A breaker, 14 AWG Cu.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • 1 kW = 3,412 BTU/h; resistance heat converts all of it. Amps = watts ÷ volts (single phase) or ÷ (volts × 1.732) (three phase); power factor 1.0.
  • Fixed electric space heating is a continuous load: conductors and breaker at 125% (NEC 424.3(B)).

Sources: NEC 2020 424.3(B); 1 kW = 3,412 BTU/h. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.