Metal roof condensation: the guide

A metal roof drips in winter when its inside face is colder than the dew point of the air in the building. The cure is in the insulation number, and the calculator tells you which number.

Open the calculator

Why this number matters

The underside of a bare metal roof is, for practical purposes, at the outside temperature, and on a clear night a few degrees below it. The air inside a working building carries moisture from people, forklifts, wet floors, propane heaters, and anything that is washed down, so its dew point is well above freezing even in a cold building. Where the two meet, on the panel, the water condenses and drips, and in a freeze it frosts and then drips when the sun comes up.

Insulation moves the inside surface toward the inside temperature: the colder-side resistance is a smaller share of the total, so the surface runs warmer. The calculator solves the steady-state surface temperature for any R-value, compares it with the dew point, and then solves backward for the R-value that keeps the surface at the dew point, which is the number to put on the order. Lowering the inside humidity by ventilation or dehumidification moves the dew point down and works just as well.

Two things the simple model does not see: thermal bridging at purlins, where the steel conducts heat through the blanket and the surface runs colder in stripes, and a blanket compressed over purlins performing at about 60% of its label. Liner systems that hold the insulation at full thickness below the purlins beat both, which is why the energy codes moved to them.

How it is figured

  • Steady-state surface temperature: inside air less the temperature difference times the inside air film's share of the total resistance (inside film R-0.61, assembly R, outside film R-0.17).
  • The surface sweats when it is below the dew point of the inside air (Magnus formula). Solving the same equation for R gives the assembly that keeps the surface at the dew point.
  • Thermal bridging at purlins and the radiant cooling of a roof under a clear sky both make the real surface colder than the average; the outside temperature hint covers the second, the first is why a liner system beats a compressed blanket.

A worked example

At 65°F and 55% humidity inside the dew point is 48°F. With 20°F outside, a bare panel's inside face sits at 36°F and drips; R-10 brings the surface to 61°F and dry, and the calculator reports that about R-2.5 would have been the dividing line, which is how little it takes, and how certain the drip is without it.

The tool's starting values, and what it returns for them:

Inside air temperature65 °F
Inside humidity55 %
Outside temperature20 °F
Roof or wall R-valueR-10 blanket
Dew point inside48.4 °F
R-value that keeps it dry0.9
Highest inside humidity at this R-value91 % RH

How to take the readings

  1. Early morning after a clear cold night, hang a thermo-hygrometer at head height inside and read temperature and humidity.
  2. Read the outside temperature from a thermometer in the shade, and take 5°F off it for a roof under a clear sky.
  3. Check the drawings or the insulation tag for the roof R-value; a compressed R-19 blanket over purlins performs nearer R-13.

Tools: thermo-hygrometer, outdoor thermometer, the building drawings

Mistakes that catch people

  • Specifying a radiant barrier or bubble foil to stop condensation: its real R is small and the surface stays cold.
  • Forgetting the vapor retarder: insulation without a facing on the warm side moves the condensation into the blanket.
  • Measuring the outside temperature only: a clear night radiates a roof 5 to 10°F below the air.

Rules of thumb

  • Bare metal roof: drips whenever the outside is colder than the inside dew point, which in a working building is most winter nights.
  • A draped R-19 blanket performs near R-13; a liner system holds its label.
  • Inside humidity above 60% in winter means a moisture source to find.

When to stop calculating and make a call

  • The building is cold storage or a dry room: the vapor barrier is on the other side and the design is an engineer's.
  • Water is already staining the insulation facing: the moisture source and the facing's integrity need a look before the R-value.

Questions people ask

Why does an uninsulated metal roof drip in winter?
The roof panel is nearly at the outside temperature; on a clear night it is colder than the air. Any moisture in the building (people, forklifts, wet floors, propane heaters, unvented gas) raises the inside dew point, and the panel underside is well below it, so the water condenses and drips. A bare panel at 65°F inside and 55% humidity drips whenever it is colder than about 48°F.
Does a radiant barrier or bubble foil stop it?
Only a little. Its effective R-value is small, so the surface stays close to the outside temperature. The fix is real insulation with a vapor retarder on the warm side, or lower inside humidity.
What about a cold storage building?
The problem reverses: the warm, humid side is outside and the cold surface is inside the panel; the same calculation applies with the outside air as the humid air and the vapor retarder on the outside. Insulated metal panels for cold storage are built that way.

Standards and sources

  • ASHRAE Handbook, Fundamentals, Heat Transfer (surface film resistances) and Psychrometrics
  • MBMA Metal Building Systems Manual, Energy and Moisture Control

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.