Cold storage and condensation
Will the metal roof or wall sweat inside the building?
Inside temperature and humidity, outside temperature, and the roof or wall R-value in; the inside surface temperature, whether it drips, and the insulation that keeps it dry.
Read the guide: what the number means and how to use it
- Steady-state surface temperature: inside air less the temperature difference times the inside air film's share of the total resistance (inside film R-0.61, assembly R, outside film R-0.17).
- The surface sweats when it is below the dew point of the inside air (Magnus formula). Solving the same equation for R gives the assembly that keeps the surface at the dew point.
Need it quoted?
Seals, shelters, high-speed and cold storage doors, and vestibules priced as line items with freight to your dock.
Dock seals and doorsMetal roof condensation
Dew point inside
48.4 °F
surface is warmer: dry
R-value that keeps it dry
0.9
at 55% RH and 20°F outside
- Highest inside humidity at this R-value
- 91 % RH
One line for the file or the vendor
Inside 65°F/55% RH (dew point 48.4°F), outside 20°F, R-10: inside surface 62.5°F, dry; dry at R-1 or under 91% RH.
How it is figured
- Steady-state surface temperature: inside air less the temperature difference times the inside air film's share of the total resistance (inside film R-0.61, assembly R, outside film R-0.17).
- The surface sweats when it is below the dew point of the inside air (Magnus formula). Solving the same equation for R gives the assembly that keeps the surface at the dew point.
- Thermal bridging at purlins and the radiant cooling of a roof under a clear sky both make the real surface colder than the average; the outside temperature hint covers the second, the first is why a liner system beats a compressed blanket.
How to take the readings
- 1. Early morning after a clear cold night, hang a thermo-hygrometer at head height inside and read temperature and humidity.
- 2. Read the outside temperature from a thermometer in the shade, and take 5°F off it for a roof under a clear sky.
- 3. Check the drawings or the insulation tag for the roof R-value; a compressed R-19 blanket over purlins performs nearer R-13.
Tools: thermo-hygrometer, outdoor thermometer, the building drawings
Sources: ASHRAE Handbook, Fundamentals, Heat Transfer (surface film resistances) and Psychrometrics; MBMA Metal Building Systems Manual, Energy and Moisture Control. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Why does an uninsulated metal roof drip in winter?
- The roof panel is nearly at the outside temperature; on a clear night it is colder than the air. Any moisture in the building (people, forklifts, wet floors, propane heaters, unvented gas) raises the inside dew point, and the panel underside is well below it, so the water condenses and drips. A bare panel at 65°F inside and 55% humidity drips whenever it is colder than about 48°F.
- Does a radiant barrier or bubble foil stop it?
- Only a little. Its effective R-value is small, so the surface stays close to the outside temperature. The fix is real insulation with a vapor retarder on the warm side, or lower inside humidity.
- What about a cold storage building?
- The problem reverses: the warm, humid side is outside and the cold surface is inside the panel; the same calculation applies with the outside air as the humid air and the vapor retarder on the outside. Insulated metal panels for cold storage are built that way.