Dew point and condensation on a surface

Air temperature and humidity in, dew point out, with a check on whether a door, floor, pipe, or roof at a given temperature will sweat.

Read the guide: what the number means and how to use it

  • Dew point from the Magnus formula over water (coefficients 17.62 and 243.12 °C), the form used by most weather services; it is within a few tenths of a degree of the ASHRAE psychrometric tables between 0 and 120°F.
  • A surface condenses when its temperature is below the dew point of the air touching it. The highest safe humidity is the ratio of the saturation pressures at the surface and air temperatures.

Need it quoted?

Seals, shelters, high-speed and cold storage doors, and vestibules priced as line items with freight to your dock.

Dock seals and doors

Dew point and condensation

SURFACE 60°Fwet: 11.9°F below the dew pointair 85.0°Fdew point 71.9°Fsurface 60.0°Fanything colder than the dew point sweats

Dew point

71.9 °F

any surface colder than this sweats

Surface below the dew point by

11.9 °F

condensation forms

Highest humidity this surface stays dry at

43 % RH

at 85°F air

  • The surface is 11.9°F below the dew point. Dry it by lowering the humidity below 43% or warming the surface above 71.9°F.
Moisture in the air
118 grains per lb of dry air

One line for the file or the vendor

85°F at 65% RH: dew point 71.9°F; surface at 60°F condenses; dry below 43% RH.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Dew point from the Magnus formula over water (coefficients 17.62 and 243.12 °C), the form used by most weather services; it is within a few tenths of a degree of the ASHRAE psychrometric tables between 0 and 120°F.
  • A surface condenses when its temperature is below the dew point of the air touching it. The highest safe humidity is the ratio of the saturation pressures at the surface and air temperatures.
  • Moisture content in grains per pound at sea level; at altitude the dew point is unchanged and the grains read slightly high.

How to take the readings

  1. 1. Hang a digital thermo-hygrometer where the air actually meets the surface, at the dock door opening or at the floor near the cold room door, and let it settle 10 minutes.
  2. 2. Read the air temperature and relative humidity from it; do not use the thermostat across the room.
  3. 3. Point an infrared thermometer at the surface itself (door panel, floor, pipe) and read the surface temperature.

Tools: a $20 thermo-hygrometer and an infrared thermometer

Sources: Magnus-Tetens dew point approximation (Alduchov and Eskridge, 1996); ASHRAE Handbook, Fundamentals, Psychrometrics. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Why does the dock floor sweat in summer?
Warm, humid outside air comes in when the doors open and meets a concrete floor that is still at last night's temperature, or cooled by the slab. If the floor is below the dew point of that air, water condenses on it, the same way it does on a cold can. The fix is to keep the air drier than the floor's dew point limit, keep the humid air out with seals and air curtains, or warm the floor.
What dew point is safe?
Any surface that stays warmer than the dew point stays dry. On a humid summer afternoon at 85°F and 65% humidity the dew point is about 72°F, so anything at 72°F or cooler sweats: refrigerated dock floors, chilled water pipes, the inside of a cold room door, the underside of an uninsulated metal roof at night.
Does the calculator work in a freezer?
Yes, down to minus 40. Below freezing the moisture forms frost rather than water, which is what builds up on freezer door frames and evaporator coils.

Related calculators: Cold dock door condensation, Cold room door infiltration load, Metal roof condensation. All calculators.