Cold storage and condensation

Will the cold storage dock door or floor sweat?

Outside air, the cold room temperature, and the door or floor surface in; whether it sweats, the dew point, and the humidity or surface temperature that keeps it dry out.

Read the guide: what the number means and how to use it

  • Dew point of the dock air from its temperature and humidity (Magnus formula). The door face, frame, and threshold sweat when they are colder than that dew point.
  • The highest humidity the surface tolerates is the saturation pressure at the surface temperature divided by the saturation pressure at the air temperature.

Need it quoted?

Seals, shelters, high-speed and cold storage doors, and vestibules priced as line items with freight to your dock.

Dock seals and doors

Cold dock door condensation

SURFACE 50°Fwet: 22.4°F below the dew pointair 88.0°Fdew point 72.4°Fsurface 50.0°Fanything colder than the dew point sweats

Dew point of the dock air

72.4 °F

Door or floor

sweats

surface 50°F vs dew point 72.4°F

Keep the dock air under

27 % RH

to stay dry at this surface temperature

  • At 88°F and 60% the dew point is 72.4°F and the surface is 50°F, so it sweats. Either dry the dock air below 27% RH (dehumidifier or conditioned vestibule), keep the humid air off the door (dock seals, air curtain, fast door), or heat the surface above 72.4°F (heated frames and thresholds).
Or warm the surface above
72.4 °F

One line for the file or the vendor

Dock air 88°F / 60% RH, dew point 72.4°F; cold room 35°F; surface 50°F sweats; dry below 27% RH or above 72.4°F surface.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Dew point of the dock air from its temperature and humidity (Magnus formula). The door face, frame, and threshold sweat when they are colder than that dew point.
  • The highest humidity the surface tolerates is the saturation pressure at the surface temperature divided by the saturation pressure at the air temperature.
  • Cold room doors are insulated, so the outside face sits well above the room temperature; measure it rather than assuming the room temperature.

How to take the readings

  1. 1. On a humid afternoon with the dock door open, hang a thermo-hygrometer at the door opening and let it settle 10 minutes; read air temperature and humidity.
  2. 2. Read the cold room setpoint from its controller.
  3. 3. Point an infrared thermometer at the outside face of the cold room door, its frame, and the floor at the threshold; use the coldest of the three.

Tools: thermo-hygrometer, infrared thermometer

Sources: Magnus-Tetens dew point approximation; ASHRAE Handbook, Refrigeration, refrigerated facility design (doors, vestibules, and condensation control). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Why does the cold room door sweat on the outside?
The outside face of the door is cooled from behind by the room. When the dock air's dew point is higher than that face temperature, moisture condenses on it. The three fixes are the three terms in the calculation: drier air, a warmer surface, or keeping the humid air away from the door with seals, a vestibule, or an air curtain.
What humidity should a refrigerated dock hold?
Low enough that the dew point of the dock air stays under the coldest surface the air touches. On a 35°F cooler with a door face at 50°F, that is roughly 35% humidity at 80°F dock air; the calculator gives the exact figure for your readings. Refrigerated docks are usually held at 45 to 50°F for that reason, and dehumidified in summer.
Do dock seals help with condensation?
Yes. A seal or shelter at the trailer keeps outside air out of the dock while the trailer is open, so the dock air stays at the conditioned temperature and humidity, and the door only sees that air. See the dock seal calculator for the taper and projection.

Related calculators: Dew point and condensation, Cold room door infiltration load, Dock seal slope and taper. All calculators.