Cold dock door condensation: the guide

The outside face of a cold room door sweats because it is colder than the dew point of the dock air, and there are only three fixes: drier air, a warmer surface, or keeping the humid air away from the door.

Open the calculator

Why this number matters

A cold room door is an insulated panel. The room side runs at the room temperature, the dock side somewhere between the room and the dock, typically 10 to 20°F above the room. On a 35°F cooler that puts the outside face near 50°F, and dock air at 80°F and 50% humidity has a dew point of 59°F, so the door, the frame, and the threshold run wet all summer. Freezer doors do the same thing and the water freezes, which is why freezer frames are heated.

The calculation points at the fix. Dry the dock air below the humidity at which its dew point drops under the surface temperature, which on a refrigerated dock means holding the dock at 45 to 50°F and running a dehumidifier in summer. Or warm the surface: heated frames and thresholds, air curtains that wash the face with room air. Or keep the humid air off the door: dock seals and shelters at the trailer, fast doors on the vestibule, and a vestibule in the first place.

Wet floors at a cold room door are a slip hazard and a forklift hazard, and frost on a freezer threshold stops the door from sealing; the reasons to fix it are more than cosmetic.

How it is figured

  • Dew point of the dock air from its temperature and humidity (Magnus formula). The door face, frame, and threshold sweat when they are colder than that dew point.
  • The highest humidity the surface tolerates is the saturation pressure at the surface temperature divided by the saturation pressure at the air temperature.
  • Cold room doors are insulated, so the outside face sits well above the room temperature; measure it rather than assuming the room temperature.

A worked example

Dock air at 88°F and 60% has a dew point of 72°F. A cooler door face at 50°F sweats; to stay dry at that surface the dock air would have to be under 27% humidity at 88°F, which is why the practical answer is a refrigerated dock at 48°F and a dehumidifier.

The tool's starting values, and what it returns for them:

Outside or dock air temperature88 °F
Outside or dock air humidity60 %
Cold room temperature35 °F
Door or floor surface temperature50 °F
Dew point of the dock air72.4 °F
Door or floorsweats
Keep the dock air under27 % RH
Or warm the surface above72.4 °F
  • At 88°F and 60% the dew point is 72.4°F and the surface is 50°F, so it sweats. Either dry the dock air below 27% RH (dehumidifier or conditioned vestibule), keep the humid air off the door (dock seals, air curtain, fast door), or heat the surface above 72.4°F (heated frames and thresholds).

How to take the readings

  1. On a humid afternoon with the dock door open, hang a thermo-hygrometer at the door opening and let it settle 10 minutes; read air temperature and humidity.
  2. Read the cold room setpoint from its controller.
  3. Point an infrared thermometer at the outside face of the cold room door, its frame, and the floor at the threshold; use the coldest of the three.

Tools: thermo-hygrometer, infrared thermometer

Mistakes that catch people

  • Assuming the door face is at the room temperature: measure it; the number is usually 10 to 20°F warmer, which changes the answer.
  • Sealing the door harder when the problem is the dock air.
  • Running an unheated freezer door frame in a humid dock and treating the frost as a maintenance issue.

Rules of thumb

  • Refrigerated docks run 45 to 50°F and 50% humidity or lower.
  • Freezer door frames and thresholds are heated; cooler frames usually are not, unless the dock is humid.
  • A seal at the trailer keeps outside air out; a vestibule keeps dock air out of the room.

When to stop calculating and make a call

  • Designing a refrigerated dock: the dehumidification and vestibule design is a refrigeration contractor's job.
  • Frost inside a freezer room's door or wall: that is a vapor barrier failure, not a dew point question.

Questions people ask

Why does the cold room door sweat on the outside?
The outside face of the door is cooled from behind by the room. When the dock air's dew point is higher than that face temperature, moisture condenses on it. The three fixes are the three terms in the calculation: drier air, a warmer surface, or keeping the humid air away from the door with seals, a vestibule, or an air curtain.
What humidity should a refrigerated dock hold?
Low enough that the dew point of the dock air stays under the coldest surface the air touches. On a 35°F cooler with a door face at 50°F, that is roughly 35% humidity at 80°F dock air; the calculator gives the exact figure for your readings. Refrigerated docks are usually held at 45 to 50°F for that reason, and dehumidified in summer.
Do dock seals help with condensation?
Yes. A seal or shelter at the trailer keeps outside air out of the dock while the trailer is open, so the dock air stays at the conditioned temperature and humidity, and the door only sees that air. See the dock seal calculator for the taper and projection.

Standards and sources

  • Magnus-Tetens dew point approximation
  • ASHRAE Handbook, Refrigeration, refrigerated facility design (doors, vestibules, and condensation control)

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.