Cold storage and condensation · guide
Dew point and condensation: the guide
Water appears on anything colder than the dew point of the air around it. Know the dew point and you know which doors, floors, pipes, and roofs will sweat before they do.
Why this number matters
Air holds water vapor up to a limit that depends on temperature; the dew point is the temperature at which the air you have would be saturated. Cool a surface below that and the vapor condenses on it, which is why a cold can sweats in July and a dock floor sweats on the first humid morning of spring. The air temperature itself does not matter; the moisture content, expressed as a dew point, does.
In a building the surfaces that run cold are predictable: the floor of a refrigerated dock, the frame of a cold room door, chilled water pipes, the underside of a metal roof at night, anything in a conditioned room that faces unconditioned air. The calculator takes the air's temperature and humidity, gives the dew point, and compares it with the surface temperature you read with an infrared thermometer. The difference tells you how far you are from wet, and the highest humidity the surface can tolerate tells you what the dehumidifier has to hold.
The same arithmetic runs in reverse in cold storage, where the cold surface is inside the panel and the humid air is outside, and in a dry room, where the dew point is held so low that the question is how many grams of water an hour the people and the doors bring in.
How it is figured
- Dew point from the Magnus formula over water (coefficients 17.62 and 243.12 °C), the form used by most weather services; it is within a few tenths of a degree of the ASHRAE psychrometric tables between 0 and 120°F.
- A surface condenses when its temperature is below the dew point of the air touching it. The highest safe humidity is the ratio of the saturation pressures at the surface and air temperatures.
- Moisture content in grains per pound at sea level; at altitude the dew point is unchanged and the grains read slightly high.
A worked example
At 85°F and 65% humidity the dew point is 72°F; a dock floor that is still at 60°F from the night sweats, and it stays wet until the air is drier than about 43% or the floor warms past 72.
The tool's starting values, and what it returns for them:
| Air temperature | 85 °F |
| Relative humidity | 65 % |
| Surface temperature | 60 °F |
| Dew point | 71.9 °F |
| Surface below the dew point by | 11.9 °F |
| Highest humidity this surface stays dry at | 43 % RH |
| Moisture in the air | 118 grains per lb of dry air |
- The surface is 11.9°F below the dew point. Dry it by lowering the humidity below 43% or warming the surface above 71.9°F.
How to take the readings
- Hang a digital thermo-hygrometer where the air actually meets the surface, at the dock door opening or at the floor near the cold room door, and let it settle 10 minutes.
- Read the air temperature and relative humidity from it; do not use the thermostat across the room.
- Point an infrared thermometer at the surface itself (door panel, floor, pipe) and read the surface temperature.
Tools: a $20 thermo-hygrometer and an infrared thermometer
Mistakes that catch people
- Reading humidity at the thermostat across the room and the surface at the door; measure both where the air meets the surface.
- Treating relative humidity as the number: 60% at 90°F is a 74°F dew point, 60% at 60°F is 46°F.
- Chasing condensation with heat alone: warming the air without drying it raises nothing but the bill.
Rules of thumb
- Dew point ≈ air temperature − (100 − RH) ÷ 5, roughly, above 50% RH.
- A surface 5°F above the dew point stays dry through most swings.
- Summer dock air at 85°F and 65% has a 72°F dew point: refrigerated floors will sweat.
When to stop calculating and make a call
- The surface is a cold storage panel or a dry room wall: the vapor retarder design is an engineering question.
- Mold or corrosion has already started: the fix is drier air, and the dehumidification load is a design job.
Questions people ask
- Why does the dock floor sweat in summer?
- Warm, humid outside air comes in when the doors open and meets a concrete floor that is still at last night's temperature, or cooled by the slab. If the floor is below the dew point of that air, water condenses on it, the same way it does on a cold can. The fix is to keep the air drier than the floor's dew point limit, keep the humid air out with seals and air curtains, or warm the floor.
- What dew point is safe?
- Any surface that stays warmer than the dew point stays dry. On a humid summer afternoon at 85°F and 65% humidity the dew point is about 72°F, so anything at 72°F or cooler sweats: refrigerated dock floors, chilled water pipes, the inside of a cold room door, the underside of an uninsulated metal roof at night.
- Does the calculator work in a freezer?
- Yes, down to minus 40. Below freezing the moisture forms frost rather than water, which is what builds up on freezer door frames and evaporator coils.
Standards and sources
- Magnus-Tetens dew point approximation (Alduchov and Eskridge, 1996)
- ASHRAE Handbook, Fundamentals, Psychrometrics
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.