Cold room door infiltration load: the guide

An open freezer door moves more refrigeration load than everything else in the room put together, and the number is large enough to justify almost any door you can buy.

Open the calculator

Why this number matters

When a cold room door opens, cold dense air pours out across the floor and warm humid air flows in over the top, driven by the density difference between the two. Gosney and Olama measured it in 1975 and ASHRAE still uses their correlation: the flow goes with the door area, the square root of the door height, and the square root of the density difference, and the load is that airflow times the enthalpy difference between the air outside and the air inside. For an 8 by 10 freezer door on a summer dock the fully open rate is on the order of a hundred tons.

What saves the room is that the door is not open all the time. The load is averaged by the fraction of the hour the door stands open, reduced by a flow factor for real traffic, and cut again by whatever protects the opening: a maintained strip curtain blocks about 85%, an air curtain 70 to 90%, a fast roll-up door with a vestibule about 95%. The calculator shows the load with and without the protection, which is the business case for the door.

The moisture is the second half of the story. Every pound of humid air that comes in leaves its water on the evaporator as frost, which is defrost load and lost cooling capacity on top of the heat.

How it is figured

  • Fully open doorway rate from Gosney and Olama (1975), the correlation the ASHRAE Refrigeration Handbook recommends: 795.6 × area × (outside enthalpy − room enthalpy) × room air density × (1 − outside density / room density)^0.5 × (g × height)^0.5 × Fm, with Fm = [2 / (1 + (room density / outside density)^(1/3))]^1.5.
  • Averaged over the hour by the open-time fraction and a doorway flow factor (0.8 for the usual cyclic traffic, 1.1 when the temperature difference is under 20°F), then reduced by the protective device's effectiveness.
  • Enthalpies and densities from the temperature and humidity on each side at sea level.

A worked example

An 8 by 10 door on a 0°F freezer facing a 90°F, 50% dock passes about 1.5 million BTU/h, 120 tons, while it stands open. Ten minutes an hour of traffic with no protection averages to 16 tons; a fast door with a vestibule at 95% cuts that under a ton.

The tool's starting values, and what it returns for them:

Door width8' 0"
Door height10' 0"
Cold room temperature0 °F
Cold room humidity90 %
Air outside the door90 °F
Humidity outside the door50 %
Door open time10 min per hour
Doorway protectionNone, open doorway
Infiltration load16.1 tons
Load with no protection193,149 BTU/h
Saved by the protection0 tons
Rate while the door stands open1,448,619 BTU/h
Enthalpy difference, outside less room37.3 BTU/lb dry air
Doorway flow factor used0.8
  • 16.1 tons is a large share of a typical room's load; shorter open times, a fast door, or a vestibule pay back quickly.

How to get the open time

  1. Count door cycles in a busy hour from the door controller's cycle counter or by watching.
  2. Time a few openings with a stopwatch, from the door starting to open until it is closed again; a fast door is 10 to 20 seconds, a slide door with a forklift pass 30 to 60.
  3. Multiply cycles by seconds and divide by 60 for minutes per hour; use the busiest hour for sizing.

Tools: a stopwatch and the door's cycle counter

Mistakes that catch people

  • Counting the door as closed because it has a strip curtain: torn or tied-back strips are an open door.
  • Timing door openings from memory; the door controller's counter and a stopwatch give the real number.
  • Sizing the refrigeration without the door load and discovering the room cannot hold temperature on a busy afternoon.

Rules of thumb

  • Fully open freezer door, summer dock: roughly 10 to 15 tons per square meter of opening.
  • Strip curtains about 85% effective when maintained, zero when not.
  • A fast door with an airlock is the best refrigeration investment on a busy freezer.

When to stop calculating and make a call

  • The room is being designed or the compressor replaced: the contractor runs the full load with product, people, and defrost.
  • The door is a dry room or cleanroom boundary: moisture, not heat, is the load that matters.

Questions people ask

How much does an open freezer door cost?
A standard 8 by 10 foot freezer door at 0°F standing open to a 90°F, 50% humidity dock takes on the order of 120 tons of refrigeration while it is open, which is why the load drops so steeply with open time and why a fast door with a vestibule, at roughly 95% effectiveness, is usually the best money spent on a cold room.
Are strip curtains worth it?
In the ASHRAE ranges a maintained strip curtain blocks about 85% of the infiltration, which the calculator shows as tons saved. The qualifier is maintained: torn, missing, or tied-back strips drop toward zero. Air curtains run lower, 70 to 90% depending on the unit and how it is set.
Why does humidity matter if the temperatures are the same?
The load is driven by the enthalpy difference, and most of the enthalpy in warm summer air is its moisture. Humid dock air also leaves its water on the evaporator as frost, which is defrost load on top of what is shown here.

Standards and sources

  • Gosney, W.B. and Olama, H.A.L., Heat and enthalpy gains through cold room doorways, Proc. Inst. Refrig., 1975
  • ASHRAE Handbook, Refrigeration, Refrigerated-Facility Loads (infiltration air load, doorway flow and protection factors)

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.