Refrigeration load from an open cold room door

Door size, room and outside conditions, and how long the door stands open each hour in; the infiltration load in BTU/h and tons, with and without strip curtains, air curtains, or a fast door.

Read the guide: what the number means and how to use it

  • Fully open doorway rate from Gosney and Olama (1975), the correlation the ASHRAE Refrigeration Handbook recommends: 795.6 × area × (outside enthalpy − room enthalpy) × room air density × (1 − outside density / room density)^0.5 × (g × height)^0.5 × Fm, with Fm = [2 / (1 + (room density / outside density)^(1/3))]^1.5.
  • Averaged over the hour by the open-time fraction and a doorway flow factor (0.8 for the usual cyclic traffic, 1.1 when the temperature difference is under 20°F), then reduced by the protective device's effectiveness.

Need it quoted?

Seals, shelters, high-speed and cold storage doors, and vestibules priced as line items with freight to your dock.

Dock seals and doors

Cold room door infiltration load

COLD ROOM 0°FOUTSIDE 90°F8' × 10' door16.1 tons of refrigeration while open

Infiltration load

16.1 tons

193,149 BTU/h averaged over the hour

Load with no protection

193,149 BTU/h

16.1 tons

Saved by the protection

0 tons

  • 16.1 tons is a large share of a typical room's load; shorter open times, a fast door, or a vestibule pay back quickly.
Rate while the door stands open
1,448,619 BTU/h120.7 tons, 80 sq ft opening
Enthalpy difference, outside less room
37.3 BTU/lb dry air
Doorway flow factor used
0.8

One line for the file or the vendor

8' x 10' door, room 0°F/90%, outside 90°F/50%, open 10 min/h, protection 0%: infiltration 16.1 tons (193,149 BTU/h).

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Fully open doorway rate from Gosney and Olama (1975), the correlation the ASHRAE Refrigeration Handbook recommends: 795.6 × area × (outside enthalpy − room enthalpy) × room air density × (1 − outside density / room density)^0.5 × (g × height)^0.5 × Fm, with Fm = [2 / (1 + (room density / outside density)^(1/3))]^1.5.
  • Averaged over the hour by the open-time fraction and a doorway flow factor (0.8 for the usual cyclic traffic, 1.1 when the temperature difference is under 20°F), then reduced by the protective device's effectiveness.
  • Enthalpies and densities from the temperature and humidity on each side at sea level.

How to get the open time

  1. 1. Count door cycles in a busy hour from the door controller's cycle counter or by watching.
  2. 2. Time a few openings with a stopwatch, from the door starting to open until it is closed again; a fast door is 10 to 20 seconds, a slide door with a forklift pass 30 to 60.
  3. 3. Multiply cycles by seconds and divide by 60 for minutes per hour; use the busiest hour for sizing.

Tools: a stopwatch and the door's cycle counter

Sources: Gosney, W.B. and Olama, H.A.L., Heat and enthalpy gains through cold room doorways, Proc. Inst. Refrig., 1975; ASHRAE Handbook, Refrigeration, Refrigerated-Facility Loads (infiltration air load, doorway flow and protection factors). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

How much does an open freezer door cost?
A standard 8 by 10 foot freezer door at 0°F standing open to a 90°F, 50% humidity dock takes on the order of 120 tons of refrigeration while it is open, which is why the load drops so steeply with open time and why a fast door with a vestibule, at roughly 95% effectiveness, is usually the best money spent on a cold room.
Are strip curtains worth it?
In the ASHRAE ranges a maintained strip curtain blocks about 85% of the infiltration, which the calculator shows as tons saved. The qualifier is maintained: torn, missing, or tied-back strips drop toward zero. Air curtains run lower, 70 to 90% depending on the unit and how it is set.
Why does humidity matter if the temperatures are the same?
The load is driven by the enthalpy difference, and most of the enthalpy in warm summer air is its moisture. Humid dock air also leaves its water on the evaporator as frost, which is defrost load on top of what is shown here.

Related calculators: Cold room refrigeration load, Cold dock door condensation, Dew point and condensation. All calculators.