Air, heating, and ventilation · guide
Destratification savings: the guide
Warm air stacks under the deck of a tall building and leaks out through the roof; a fan that mixes it back down lowers the average temperature the building loses heat at, and the saving shows up on the gas bill.
Why this number matters
In a 30-foot warehouse heated by unit heaters the air at the deck can run 20°F warmer than at the floor. Heat loss through the roof follows the temperature at the roof, so the building is paying to keep the ceiling warm while the thermostat at five feet asks for more. Mixing the column with slow fans brings the deck air down to the floor, where the people are, and the whole volume settles a degree or two above the setpoint; the average temperature the envelope sees drops, and the heat loss with it.
The rule of thumb behind the estimate is about 3% of heating energy per degree of average building temperature, a figure that shows up across the energy guidance. Field results for destratification run 10 to 30%, and the calculator ties the estimate to the stratification you measure rather than to a brochure. Buildings with high ceilings, unit heaters, and uninsulated roofs gain the most; low, well-mixed, radiant-heated buildings gain little.
The fans that do this are the same HVLS fans that cool in summer, run at a crawl, or small dedicated destratification fans hung at the deck; either way the fan's own power is a few hundred watts against thousands of therms.
How it is figured
- Stratification is the ceiling temperature less the floor temperature. Before mixing, the average air temperature is about the midpoint; after, the whole column sits a degree or two above the floor setpoint.
- Heat loss through the roof and walls follows the inside air temperature, so cutting the average cuts the loss: taken as 3% of heating energy per °F of average reduction, capped at 30%, the range reported for destratification fans.
A worked example
A 30-foot building at 60°F on the floor and 80 at the deck averages about 70; mixed, it averages about 61.5. The 8.5-degree drop at 3% a degree is about 26% of a $24,000 heating bill, $6,100 a year.
The tool's starting values, and what it returns for them:
| Ceiling height | 30 ft |
| Temperature at the floor | 60 °F |
| Temperature at the ceiling | 80 °F |
| Heating cost per year | 24,000 $ |
| Heating saved per year | 6,120 $ |
| Stratification now | 20 °F |
| Average air temperature cut | 8.5 °F |
| Saving | 26 % |
How to measure stratification
- On a cold morning with the heat running, read the thermostat or a thermometer at 5 ft for the floor temperature.
- Read the air temperature at the deck: a probe thermometer on a pole or lift, or an infrared thermometer on the underside of the roof deck as a proxy.
- Note the heating bill for the last 12 months from the gas or electric statements.
Tools: probe thermometer and a pole, or an infrared thermometer; the utility bills
Mistakes that catch people
- Measuring the deck temperature on a mild day; take it on a cold morning with the heaters working.
- Expecting the saving in a radiant-heated building, where the air is barely warmed.
- Running the fans at summer speed in winter and chilling the floor crew.
Rules of thumb
- 0.5 to 1°F per foot of height is typical stratification under unit heaters.
- About 3% of heating energy per degree of average temperature.
- 10 to 20% is the usual result; 30 at the top.
When to stop calculating and make a call
- Rooftop units with high returns: the mechanical engineer may rebalance the returns instead.
- Sprinkler and crane clearances for the fans, as with any ceiling fan.
Questions people ask
- How much warmer is the ceiling than the floor?
- In a 30 ft warehouse heated by unit heaters, 15 to 25°F is common: warm air rises and sits under the deck, where it leaks out through the roof at the highest rate. Destratification fans or HVLS fans run slowly bring it back down.
- Is 30% realistic?
- It is the top of the range in field studies, for tall unmixed buildings with a lot of roof. 10 to 20% is the usual outcome; the calculator ties the estimate to the stratification you actually measure.
Standards and sources
- U.S. DOE / Federal Energy Management Program, destratification fan guidance
- Rule of thumb: about 3% heating energy per °F of indoor temperature (ENERGY STAR building guidance)
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.