Air, heating, and ventilation

Ventilation for propane and gas forklifts indoors

Trucks running inside and the building size in; the dilution cfm by the ACGIH rule, the air changes that is, and the fans.

Read the guide: what the number means and how to use it

  • Dilution ventilation per truck in operation from the ACGIH Industrial Ventilation manual: 10,000 cfm per propane-fueled lift truck and 16,000 per gasoline truck, average operating conditions.
  • Divided into the building volume for the equivalent air change rate, and by the fan rating for the fan count.

Need it quoted?

HVLS fans, unit heaters, and ventilation priced with installation as line items.

Request a quote

Forklift exhaust ventilation

dilution cfm40,000 cfm

Dilution airflow

40,000 cfm

ACGIH: 10,000 per propane truck, 16,000 per gasoline

Air changes per hour that is

1.9

Exhaust fans

2

at 20,000 cfm each, plus matching intake

Building volume
1,260,000 cu ft

One line for the file or the vendor

4 propane + 0 gasoline trucks in 1,260,000 cu ft: 40,000 cfm dilution (1.9 ACH), 2 fans at 20,000 cfm.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Dilution ventilation per truck in operation from the ACGIH Industrial Ventilation manual: 10,000 cfm per propane-fueled lift truck and 16,000 per gasoline truck, average operating conditions.
  • Divided into the building volume for the equivalent air change rate, and by the fan rating for the fan count.

Sources: ACGIH, Industrial Ventilation: A Manual of Recommended Practice for Design, dilution ventilation for internal combustion lift trucks; OSHA 1910.178 (powered industrial trucks) and CO exposure limits (1910.1000). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Is 10,000 cfm per forklift really needed?
That is the ACGIH design figure for an average propane truck in good tune; older guidance said 5,000. Tuning, catalytic mufflers, and CO monitors with alarms let many plants run less with a documented program, which is a call for the safety officer, not a calculator.
What about electric trucks?
No exhaust, but the charging room needs hydrogen ventilation: see the air changes calculator at 6 per hour, or the battery maker's rule by charger amp-hours.