Forklift exhaust ventilation: the guide

Propane forklifts make carbon monoxide; the industrial ventilation rule is 10,000 cfm of dilution per truck running inside, and the building volume tells you what that means in air changes.

Open the calculator

Why this number matters

A propane engine in good tune still produces enough carbon monoxide to raise a closed warehouse past the exposure limits in an hour or two. The ACGIH Industrial Ventilation manual sets the dilution rate at 10,000 cfm per propane-fueled lift truck in operation and 16,000 per gasoline truck, averaged operating conditions; the older 5,000-cfm figure still circulates and is out of date. Multiply by the trucks running at once, and the building volume turns it into an air change rate that is often under one an hour in a big warehouse, which is why CO does not read high in the open floor and does in the dock vestibule.

Dilution is the blunt instrument. Tuning and catalytic mufflers cut the source, CO monitors with alarms in the low spots catch the accumulation, and electric trucks remove it; most plants running propane indoors keep a documented program of all three and ventilate to the rule or a documented alternative.

The calculator gives the fan count the rule implies and the air changes that is, so the ventilation designer and the safety officer are looking at the same number.

How it is figured

  • Dilution ventilation per truck in operation from the ACGIH Industrial Ventilation manual: 10,000 cfm per propane-fueled lift truck and 16,000 per gasoline truck, average operating conditions.
  • Divided into the building volume for the equivalent air change rate, and by the fan rating for the fan count.

A worked example

Four propane trucks running at once need 40,000 cfm of dilution; in a 300 by 150 by 28 foot building that is 1.9 air changes an hour and two 20,000-cfm exhaust fans with matching intake.

The tool's starting values, and what it returns for them:

Propane trucks running at once4
Gasoline trucks running at once0
Building length300 ft
Building width150 ft
Clear height28 ft
Exhaust fan rating20,000 cfm
Dilution airflow40,000 cfm
Air changes per hour that is1.9
Exhaust fans2
Building volume1,260,000 cu ft

Mistakes that catch people

  • Counting the fleet instead of the trucks running at once.
  • Ventilating the open floor and leaving the dock vestibule and the trailer interiors, where CO actually accumulates, unmonitored.
  • Treating a tuned engine as no engine; the rule assumes a tuned one.

Rules of thumb

  • 10,000 cfm per propane truck, 16,000 per gasoline (ACGIH).
  • CO monitors in low and enclosed areas regardless of the fans.
  • Electric trucks: no CO, but the charging room needs hydrogen ventilation.

When to stop calculating and make a call

  • Setting a lower rate with monitoring and tuning: the safety officer documents it against OSHA's CO limits.
  • Trailers loaded by propane trucks: that is a confined space question.

Questions people ask

Is 10,000 cfm per forklift really needed?
That is the ACGIH design figure for an average propane truck in good tune; older guidance said 5,000. Tuning, catalytic mufflers, and CO monitors with alarms let many plants run less with a documented program, which is a call for the safety officer, not a calculator.
What about electric trucks?
No exhaust, but the charging room needs hydrogen ventilation: see the air changes calculator at 6 per hour, or the battery maker's rule by charger amp-hours.

Standards and sources

  • ACGIH, Industrial Ventilation: A Manual of Recommended Practice for Design, dilution ventilation for internal combustion lift trucks
  • OSHA 1910.178 (powered industrial trucks) and CO exposure limits (1910.1000)

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.