HVAC size for an in-plant or modular office

Office size, people, equipment, windows, and the plant it sits in; the cooling load in BTU/h and tons, the heating load, and the unit to ask for.

Read the guide: what the number means and how to use it

  • Cooling: panel and ceiling conduction at the plant-to-office temperature difference (R-10 panels, 0.3 BTU/h per sq ft per °F, 0.5 with sun), 450 BTU/h per person, 3.412 BTU/h per watt of equipment, lighting at 1.2 W per sq ft, glass at 15 BTU/h per sq ft inside a plant or 60 with sun, outside air at 7.5 cfm per person, plus 10%.
  • Heating: the same envelope at the winter difference to 70°F plus the ventilation air. Packaged units come in half-ton steps to 5 tons, then 6, 7.5, 10.

Need it quoted?

In-plant offices sized to the headcount, pre-wired, with HVAC and restrooms, priced as line items.

Modular offices

Office HVAC BTU

0 tons10 tons1.32 tonscooling load

Cooling

1.32 tons

15,807 BTU/h

Unit to ask for

2 tons

wall-mount or rooftop packaged unit

Heating

7,272 BTU/h

2.1 kW electric

Through the panels and ceiling
4,968 BTU/h
People, equipment, lights
7,467 BTU/h
Glass
720 BTU/h
Square feet per ton
292

One line for the file or the vendor

24x16 ft office, 4 people, 1200 W, 48 sq ft glass, plant 90°F summer / 50°F winter: cooling 15,807 BTU/h (1.32 tons, 1.5 ton unit), heating 7,272 BTU/h.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Cooling: panel and ceiling conduction at the plant-to-office temperature difference (R-10 panels, 0.3 BTU/h per sq ft per °F, 0.5 with sun), 450 BTU/h per person, 3.412 BTU/h per watt of equipment, lighting at 1.2 W per sq ft, glass at 15 BTU/h per sq ft inside a plant or 60 with sun, outside air at 7.5 cfm per person, plus 10%.
  • Heating: the same envelope at the winter difference to 70°F plus the ventilation air. Packaged units come in half-ton steps to 5 tons, then 6, 7.5, 10.

Sources: ASHRAE Handbook, Fundamentals, Nonresidential Cooling and Heating Load Calculations (simplified); ASHRAE 62.1 (outdoor air: 5 cfm per person plus 0.06 cfm per sq ft, offices). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

Why does an in-plant office need so much cooling?
It sits inside a hot plant: every panel faces 90 or 100°F air all day, and four people with computers add a ton of their own. A 24 by 16 office in a hot plant lands at 2 to 3 tons, double what the same office needs in a conditioned building.

Related calculators: Office size for headcount, Office circuits and panel, Electricity cost. All calculators.