Offices, people, and code
HVAC size for an in-plant or modular office
Office size, people, equipment, windows, and the plant it sits in; the cooling load in BTU/h and tons, the heating load, and the unit to ask for.
Read the guide: what the number means and how to use it
- Cooling: panel and ceiling conduction at the plant-to-office temperature difference (R-10 panels, 0.3 BTU/h per sq ft per °F, 0.5 with sun), 450 BTU/h per person, 3.412 BTU/h per watt of equipment, lighting at 1.2 W per sq ft, glass at 15 BTU/h per sq ft inside a plant or 60 with sun, outside air at 7.5 cfm per person, plus 10%.
- Heating: the same envelope at the winter difference to 70°F plus the ventilation air. Packaged units come in half-ton steps to 5 tons, then 6, 7.5, 10.
Need it quoted?
In-plant offices sized to the headcount, pre-wired, with HVAC and restrooms, priced as line items.
Modular officesOffice HVAC BTU
Cooling
1.32 tons
15,807 BTU/h
Unit to ask for
2 tons
wall-mount or rooftop packaged unit
Heating
7,272 BTU/h
2.1 kW electric
- Through the panels and ceiling
- 4,968 BTU/h
- People, equipment, lights
- 7,467 BTU/h
- Glass
- 720 BTU/h
- Square feet per ton
- 292
One line for the file or the vendor
24x16 ft office, 4 people, 1200 W, 48 sq ft glass, plant 90°F summer / 50°F winter: cooling 15,807 BTU/h (1.32 tons, 1.5 ton unit), heating 7,272 BTU/h.
How it is figured
- Cooling: panel and ceiling conduction at the plant-to-office temperature difference (R-10 panels, 0.3 BTU/h per sq ft per °F, 0.5 with sun), 450 BTU/h per person, 3.412 BTU/h per watt of equipment, lighting at 1.2 W per sq ft, glass at 15 BTU/h per sq ft inside a plant or 60 with sun, outside air at 7.5 cfm per person, plus 10%.
- Heating: the same envelope at the winter difference to 70°F plus the ventilation air. Packaged units come in half-ton steps to 5 tons, then 6, 7.5, 10.
Sources: ASHRAE Handbook, Fundamentals, Nonresidential Cooling and Heating Load Calculations (simplified); ASHRAE 62.1 (outdoor air: 5 cfm per person plus 0.06 cfm per sq ft, offices). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Why does an in-plant office need so much cooling?
- It sits inside a hot plant: every panel faces 90 or 100°F air all day, and four people with computers add a ton of their own. A 24 by 16 office in a hot plant lands at 2 to 3 tons, double what the same office needs in a conditioned building.