Offices, people, and code · guide
Office HVAC BTU: the guide
An in-plant office is an insulated box inside a hot building, and its cooling load is set by the plant around it as much as by the people and computers inside.
Why this number matters
The office panels face plant air that may be 95°F in summer, so conduction through every wall and the ceiling is a steady load all day, unlike an office in a conditioned building. Add 450 BTU/h for each person, 3.4 for every watt of computers and printers, the lights, the glass, and the outside air the people need, and a 24 by 16 office lands at two to three tons, double what the same office needs in a conditioned space. The packaged units that serve them come in half-ton steps to 5 tons, wall-mounted through a panel or set on the office roof.
Heating is the winter version: the same panels facing a 50°F plant, plus warming the ventilation air, which for a small office is a few kilowatts of electric heat in the same unit. The square feet per ton the calculator reports is a sanity check against the usual 150 to 250 for an in-plant office.
The thing to tell the office maker is the plant temperature, summer and winter; the headcount and equipment they will ask for.
How it is figured
- Cooling: panel and ceiling conduction at the plant-to-office temperature difference (R-10 panels, 0.3 BTU/h per sq ft per °F, 0.5 with sun), 450 BTU/h per person, 3.412 BTU/h per watt of equipment, lighting at 1.2 W per sq ft, glass at 15 BTU/h per sq ft inside a plant or 60 with sun, outside air at 7.5 cfm per person, plus 10%.
- Heating: the same envelope at the winter difference to 70°F plus the ventilation air. Packaged units come in half-ton steps to 5 tons, then 6, 7.5, 10.
A worked example
A 24 by 16 office with four people, 1,200 watts of equipment, 48 square feet of glass, in a 90°F plant: about 15,800 BTU/h of cooling, 1.3 tons, so a 1.5-ton unit; heating against a 50°F plant about 7,000 BTU/h, 2 kW of electric heat.
The tool's starting values, and what it returns for them:
| Office length | 24 ft |
| Office width | 16 ft |
| People | 4 |
| Computers, printers, equipment | 1,200 W |
| Window area | 48 sq ft |
| Plant temperature in summer | 90 °F |
| Plant temperature in winter | 50 °F |
| Office ceiling | Inside the plant, dust cover roof (no sun) |
| Cooling | 1.32 tons |
| Unit to ask for | 1.5 tons |
| Heating | 7,272 BTU/h |
| Through the panels and ceiling | 4,968 BTU/h |
| People, equipment, lights | 7,467 BTU/h |
| Glass | 720 BTU/h |
| Square feet per ton | 292 |
Mistakes that catch people
- Sizing by square feet as if the office were in a conditioned building.
- Forgetting the plant-side windows, which take sun if the office is by a dock door.
- No ventilation air: four people in a sealed 384-square-foot box run out of fresh air in an hour.
Rules of thumb
- In a hot plant: 150 to 250 sq ft per ton. In a conditioned building: 400 to 500.
- 450 BTU/h a person, 3.4 per watt of equipment, 1.2 W per sq ft of lighting.
- Outside air 5 cfm a person plus 0.06 per sq ft (ASHRAE 62.1).
When to stop calculating and make a call
- Offices over about 1,000 square feet or with server rooms: a mechanical engineer's load.
- Cleanroom or lab offices with pressure or filtration requirements.
Questions people ask
- Why does an in-plant office need so much cooling?
- It sits inside a hot plant: every panel faces 90 or 100°F air all day, and four people with computers add a ton of their own. A 24 by 16 office in a hot plant lands at 2 to 3 tons, double what the same office needs in a conditioned building.
Standards and sources
- ASHRAE Handbook, Fundamentals, Nonresidential Cooling and Heating Load Calculations (simplified)
- ASHRAE 62.1 (outdoor air: 5 cfm per person plus 0.06 cfm per sq ft, offices)
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.