Offices, people, and code
Restroom fixtures required by the plumbing code
Occupancy type and the occupant load in; the water closets, lavatories, drinking fountains, and service sink the International Plumbing Code requires.
Read the guide: what the number means and how to use it
- IPC Table 403.1, occupants split equally by sex (403.1.1): Business, water closets 1 per 25 for the first 50 and 1 per 50 after, lavatories 1 per 40 for the first 80 and 1 per 80 after, drinking fountain 1 per 100; Factory and Storage, 1 per 100 for water closets and lavatories, drinking fountain 1 per 400; one service sink in each.
Need it quoted?
In-plant offices sized to the headcount, pre-wired, with HVAC and restrooms, priced as line items.
Modular officesRestroom fixture count
Water closets
2 men + 2 women
urinals may replace up to 67% of the men's in B and F
Lavatories
1 men + 1 women
Drinking fountains
1
one high and one low where two or more; a bottle filler may count
- Service sink
- 1
- Occupants per sex
- 30
One line for the file or the vendor
Business at 60 occupants: 2 WC and 1 lavatories per sex, 1 drinking fountain(s), 1 service sink (IPC Table 403.1).
How it is figured
- IPC Table 403.1, occupants split equally by sex (403.1.1): Business, water closets 1 per 25 for the first 50 and 1 per 50 after, lavatories 1 per 40 for the first 80 and 1 per 80 after, drinking fountain 1 per 100; Factory and Storage, 1 per 100 for water closets and lavatories, drinking fountain 1 per 400; one service sink in each.
Sources: International Plumbing Code, Chapter 4, Table 403.1 and Section 403. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- Does the headcount or the occupant load govern?
- The occupant load from the building code, which is usually higher than the real headcount. Some officials accept the actual number of employees for a warehouse; ask before designing.
Related calculators: Occupant load and exits, Office size for headcount. All calculators.