Offices, people, and code
Occupant load and exits for a warehouse or plant
Floor area and the use in; the code occupant load, the exits required, the egress width, and the travel distance limit.
Read the guide: what the number means and how to use it
- Occupant load = floor area ÷ the occupant load factor in IBC Table 1004.5 (storage 500 gross, industrial 100 gross, business 150 gross, assembly unconcentrated 15 net).
- Exits from Table 1006.3.2 (1 up to 49 where the travel limits allow, 2 to 500, 3 to 1,000, 4 above); egress width 0.2 in per occupant for doors and 0.3 for stairs (1005.3), 32 in clear minimum per door; travel distance from Table 1017.2 and common path from Table 1006.2.1.
Need it quoted?
In-plant offices sized to the headcount, pre-wired, with HVAC and restrooms, priced as line items.
Modular officesOccupant load and exits
Occupant load
100
50,000 sq ft ÷ 500 sq ft per person
Exits required
2
spaced at least half the diagonal apart (one third when sprinklered)
Egress door width, total
20 in
0.2 in per occupant; each door at least 32 in clear
- Stair width, total
- 30 in0.3 in per occupant from a mezzanine
- Exit access travel distance limit
- 400 ft
- Common path of travel limit
- 100 ft
One line for the file or the vendor
50,000 sq ft at 500 sq ft/person, sprinklered: 100 occupants, 2 exits, 20" of door width, travel 400 ft, common path 100 ft.
How it is figured
- Occupant load = floor area ÷ the occupant load factor in IBC Table 1004.5 (storage 500 gross, industrial 100 gross, business 150 gross, assembly unconcentrated 15 net).
- Exits from Table 1006.3.2 (1 up to 49 where the travel limits allow, 2 to 500, 3 to 1,000, 4 above); egress width 0.2 in per occupant for doors and 0.3 for stairs (1005.3), 32 in clear minimum per door; travel distance from Table 1017.2 and common path from Table 1006.2.1.
Sources: International Building Code 2021, Chapter 10 (Tables 1004.5, 1005.3, 1006.2.1, 1006.3.2, 1017.2). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- My warehouse has 40 people but the code says 100. Which counts?
- The code number, for exits, egress width, and plumbing fixtures, unless the building official agrees to a posted lower load. The 500 sq ft per person storage factor is already the most generous in the table.
Related calculators: Restroom fixture count, Stair rise and run, ADA ramp length. All calculators.