How many light fixtures for a warehouse or shop
Floor size, the light level the work needs, and the fixture's lumens in; the fixture count, the grid, the spacing, and the connected watts.
Read the guide: what the number means and how to use it
- Lumen method: fixtures = foot-candles × area ÷ (lumens per fixture × coefficient of utilization × light loss factor).
- The grid is the fixture count arranged to the room's proportions; spacing should not exceed the fixture's spacing criterion times the mounting height above the work plane (check the photometric sheet).
Need it quoted?
Modular offices and equipment arrive pre-wired; tell us the service and the panel schedule comes with the quote.
Request a quoteLighting fixture count
Fixtures
40
40 by the lumen method, laid out 8 × 5
Connected load
8 kW
Lighting power density
0.4 W per sq ft
- Rows along the length
- 8
- Rows across the width
- 5
- Spacing along the length
- 25 ft
- Spacing across the width
- 20 ft
- Average foot-candles delivered
- 31 fc
One line for the file or the vendor
200x100 ft at 30 fc, 30000 lm / 200 W fixtures, CU 0.6, LLF 0.85: 40 fixtures in 8x5, 8 kW.
How it is figured
- Lumen method: fixtures = foot-candles × area ÷ (lumens per fixture × coefficient of utilization × light loss factor).
- The grid is the fixture count arranged to the room's proportions; spacing should not exceed the fixture's spacing criterion times the mounting height above the work plane (check the photometric sheet).
What to gather
- 1. Floor dimensions and the mounting height (bottom of the fixture to the floor).
- 2. The task: picking and active storage need about 30 fc at the floor, assembly 50, inspection 75 to 100 (IES).
- 3. The fixture's delivered lumens and watts from its data sheet, not the LED package lumens.
Tools: tape, the fixture cut sheet, a light meter to check afterward
Sources: IES Lighting Handbook, recommended illuminance by task; Lumen (zonal cavity) method, IES. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- How many foot-candles does a warehouse need?
- IES recommends about 10 fc for inactive storage, 20 for bulk storage and docks, 30 for active picking, and 50 for assembly or shop work, measured at the floor or the work surface. OSHA's minimum is 5 fc in general work areas (1926.56 for construction); most operations light to the IES figures.
- Why does rack height matter?
- Tall racks block light into the aisles, which the coefficient of utilization captures: 0.6 on an open floor falls to 0.4 or 0.45 between racks, and narrow-aisle fixtures aimed down the aisle do better than a flat grid.
Related calculators: LED retrofit payback, Electricity cost, Breaker size. All calculators.