Lighting fixture count: the guide

The fixture count comes from the lumen method: the light the task needs, over the area, divided by what each fixture delivers to the floor after the room and the years take their share.

Open the calculator

Why this number matters

The Illuminating Engineering Society recommends light levels by task: 10 foot-candles for inactive storage, 20 for bulk storage and docks, 30 for active picking, 50 for assembly and shops, 75 to 100 for inspection. Foot-candles times square feet is the lumens needed at the work plane; dividing by the fixture's lumens, the coefficient of utilization for how much of its light reaches the floor in this room, and the light loss factor for dirt and lamp depreciation gives the fixture count, which is then laid out in a grid that matches the room.

The coefficient of utilization is the number that changes between a warehouse and an open shop. In an open room with light walls 60% of the fixture's light lands on the floor; between tall rack rows a third of it is lost on the racks, and narrow-aisle fixtures aimed down the aisle do better than a flat grid. Spacing also has a limit, the fixture's spacing criterion times the mounting height, beyond which the floor between fixtures goes dark.

The connected kW and watts per square foot that come with the count are what the energy code and the payback calculator want, and the grid spacing is what the electrician wants.

How it is figured

  • Lumen method: fixtures = foot-candles × area ÷ (lumens per fixture × coefficient of utilization × light loss factor).
  • The grid is the fixture count arranged to the room's proportions; spacing should not exceed the fixture's spacing criterion times the mounting height above the work plane (check the photometric sheet).

A worked example

A 200 by 100 foot floor at 30 foot-candles needs 600,000 lumens at the floor; with 30,000-lumen fixtures, a CU of 0.6, and an LLF of 0.85, that is 40 fixtures in an 8 by 5 grid at 25 by 20 feet, 8 kW connected, 0.4 watts per square foot.

The tool's starting values, and what it returns for them:

Floor length200 ft
Floor width100 ft
Light level needed30 fc, active storage, picking
Fixture lumens30,000 lm
Fixture watts200 W
Coefficient of utilization0.6
Light loss factor0.85
Fixtures40
Connected load8 kW
Lighting power density0.4 W per sq ft
Rows along the length8
Rows across the width5
Spacing along the length25 ft
Spacing across the width20 ft
Average foot-candles delivered31 fc

What to gather

  1. Floor dimensions and the mounting height (bottom of the fixture to the floor).
  2. The task: picking and active storage need about 30 fc at the floor, assembly 50, inspection 75 to 100 (IES).
  3. The fixture's delivered lumens and watts from its data sheet, not the LED package lumens.

Tools: tape, the fixture cut sheet, a light meter to check afterward

Mistakes that catch people

  • Using the LED package lumens from the brochure instead of the fixture's delivered lumens from the photometric sheet.
  • A 0.6 coefficient between 30-foot racks: use 0.4 to 0.45 or aisle-specific fixtures.
  • Designing to the first-day output; the LLF is what the room looks like in year eight.

Rules of thumb

  • IES: storage 10 to 20 fc, picking 30, shop 50, inspection 75 to 100.
  • LED high bay: about 150 lumens per watt, so a 200-watt fixture is about 30,000 lumens.
  • Spacing not more than about 1.5 times the mounting height for a flat grid.

When to stop calculating and make a call

  • Rack aisles, mezzanines, and task areas: a photometric layout from the fixture maker is free and exact.
  • Emergency and egress lighting is a code design, not a lumen count.

Questions people ask

How many foot-candles does a warehouse need?
IES recommends about 10 fc for inactive storage, 20 for bulk storage and docks, 30 for active picking, and 50 for assembly or shop work, measured at the floor or the work surface. OSHA's minimum is 5 fc in general work areas (1926.56 for construction); most operations light to the IES figures.
Why does rack height matter?
Tall racks block light into the aisles, which the coefficient of utilization captures: 0.6 on an open floor falls to 0.4 or 0.45 between racks, and narrow-aisle fixtures aimed down the aisle do better than a flat grid.

Standards and sources

  • IES Lighting Handbook, recommended illuminance by task
  • Lumen (zonal cavity) method, IES

This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.