Cleanrooms and dry rooms
Cleanroom air changes, airflow, and fan filter units
Room size and the class in; the air changes per hour the class needs, the supply cfm, the number of 2x4 fan filter units, the ceiling coverage, and the fan power.
Read the guide: what the number means and how to use it
- Air change rate by class from IEST-RP-CC012 (Considerations in Cleanroom Design): ISO 8 5 to 48, ISO 7 30 to 60, ISO 6 150 to 240, ISO 5 240 to 480, ISO 4 300 to 540 per hour. Supply cfm = room volume × ACH ÷ 60.
- Fan filter units = cfm ÷ the unit's delivered airflow (a 2x4 at 90 fpm is about 720 cfm); ceiling coverage = units × 8 sq ft ÷ ceiling area, compared with the IEST coverage guidance. Fan watts become heat in the room.
Need it quoted?
See what the first-year deduction does to the payback on the same purchase.
Section 179Cleanroom air changes and FFUs
Air changes per hour
45
IEST range 30 to 60 for ISO 7
Supply airflow
2,736 cfm
2x4 fan filter units
4
2 × 2 grid, 8% of the ceiling
- Ceiling coverage
- 8 %IEST guidance 15 to 20% for ISO 7
- FFU fan power
- 0.6 kW5,256 kWh a year running 24/7
- Fan heat into the room
- 2,047 BTU/hthe HVAC has to remove it
One line for the file or the vendor
24x16x9.5 ft ISO 7 at 45 ACH: 2,736 cfm, 4 FFUs (2x2) at 720 cfm, 8% ceiling, 0.6 kW.
How it is figured
- Air change rate by class from IEST-RP-CC012 (Considerations in Cleanroom Design): ISO 8 5 to 48, ISO 7 30 to 60, ISO 6 150 to 240, ISO 5 240 to 480, ISO 4 300 to 540 per hour. Supply cfm = room volume × ACH ÷ 60.
- Fan filter units = cfm ÷ the unit's delivered airflow (a 2x4 at 90 fpm is about 720 cfm); ceiling coverage = units × 8 sq ft ÷ ceiling area, compared with the IEST coverage guidance. Fan watts become heat in the room.
Sources: IEST-RP-CC012.3, Considerations in Cleanroom Design (air change and coverage tables); ISO 14644-4, Design, construction and start-up. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- How many air changes does an ISO 7 cleanroom need?
- Thirty to sixty an hour by the IEST guidance, 45 being the usual design point; ISO 8 rooms run 15 to 25 in practice even though the range starts at 5. The right number depends on how many people and how much particle-shedding process is inside, which is why the calculator offers the low, typical, and high points.
- Fan filter units or a ducted HEPA system?
- FFUs in the ceiling grid are the modular cleanroom standard: each is its own fan and HEPA, the count sets the air changes, and adding one is an afternoon's work. Ducted systems win on energy in large rooms and on noise. A 24 by 16 ISO 7 room runs 8 to 10 FFUs.
Related calculators: ISO class from particle counts, Cleanroom recovery time, Cleanroom pressure and offset air. All calculators.