Cleanrooms and dry rooms
Cleanroom recovery time after a door opening or a spill
Air changes and how dirty the room got in; how long until it is back under its class limit, and the 100:1 recovery time ISO 14644-3 tests.
Read the guide: what the number means and how to use it
- With clean supply air the count decays exponentially: C(t) = C0 × e^(−ACH × t / 60). Time to a target = ln(C0 ÷ C1) ÷ (ACH ÷ 60), multiplied by a mixing factor because a turbulent room does not dilute as evenly as the ideal; 100:1 recovery (ISO 14644-3 B.12) is ln(100) ÷ the decay rate.
Need it quoted?
See what the first-year deduction does to the payback on the same purchase.
Section 179Cleanroom recovery time
Time to recover
3.5 min
5.7:1 down to the target
100:1 recovery time
9.2 min
the ISO 14644-3 test figure
Count halves every
1.39 min
- Dilution ratio
- 5.7
One line for the file or the vendor
45 ACH, 2,000,000 down to 352,000/m³, mixing 1.5: 3.5 min; 100:1 recovery 9.2 min.
How it is figured
- With clean supply air the count decays exponentially: C(t) = C0 × e^(−ACH × t / 60). Time to a target = ln(C0 ÷ C1) ÷ (ACH ÷ 60), multiplied by a mixing factor because a turbulent room does not dilute as evenly as the ideal; 100:1 recovery (ISO 14644-3 B.12) is ln(100) ÷ the decay rate.
Sources: ISO 14644-3:2019, Test methods, Annex B recovery test; IEST-RP-CC012, cleanroom design (recovery and air change). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- How long after a door opening is an ISO 7 room clean again?
- At 45 air changes an hour the count halves about every 1.4 minutes in a well-mixed room, so a 6:1 excursion clears in about 4 minutes and a 100:1 test takes 9 to 10. ISO 8 rooms at 15 changes take three times as long, which is the usual argument for an airlock on a busy door.
Related calculators: Cleanroom air changes and FFUs, ISO class from particle counts, Cleanroom pressure and offset air. All calculators.