Cleanrooms and dry rooms
Cleanroom ISO class from particle counts
Particle counter readings at the sizes you measured in; the ISO 14644-1 class the room meets, the limits for each class at those sizes, the Federal Standard 209E equivalent, and how far you are from the next class.
Read the guide: what the number means and how to use it
- ISO 14644-1 class limits: Cn = 10^N × (0.1 ÷ D)^2.08 particles per cubic meter at size D in µm, so at 0.5 µm ISO 5 is 3,520, ISO 6 35,200, ISO 7 352,000, ISO 8 3,520,000. The class is the smallest N whose limit your count stays under at every size you measured.
- Counters that read per cubic foot are converted at 35.3147 ft³ per m³. Federal Standard 209E classes (Class 100, 10,000, 100,000) are the particles per ft³ at 0.5 µm and map to ISO 5, 7, and 8.
Need it quoted?
See what the first-year deduction does to the payback on the same purchase.
Section 179ISO class from particle counts
Room meets
ISO Class 7
Class 10,000 in FS 209E terms; limiting size 0.5 µm
ISO 7 limit at 0.5 µm
352,000 per m³
your room: 120,000 per m³
Headroom under the limit
66 %
- ISO 6 limit at 0.5 µm
- 35,200 per m³you would need 71% fewer particles
- ISO 5 limit at 0.5 µm
- 3,520 per m³
- ISO 6
- 35,200 per m³
- ISO 7
- 352,000 per m³
- ISO 8
- 3,520,000 per m³
- Exact class number
- 6.53
One line for the file or the vendor
120,000 particles/m³ at 0.5 µm (limiting size 0.5 µm): ISO Class 7 (Class 10,000), 66% under the ISO 7 limit of 352,000.
How it is figured
- ISO 14644-1 class limits: Cn = 10^N × (0.1 ÷ D)^2.08 particles per cubic meter at size D in µm, so at 0.5 µm ISO 5 is 3,520, ISO 6 35,200, ISO 7 352,000, ISO 8 3,520,000. The class is the smallest N whose limit your count stays under at every size you measured.
- Counters that read per cubic foot are converted at 35.3147 ft³ per m³. Federal Standard 209E classes (Class 100, 10,000, 100,000) are the particles per ft³ at 0.5 µm and map to ISO 5, 7, and 8.
How to count
- 1. Run the room at rest or in operation (say which), HEPA units on, doors closed, for at least 15 minutes.
- 2. Sample with a calibrated particle counter at the number of locations ISO 14644-1 Annex A requires for the floor area (√area in m² rounded up, minimum per the table), 1 minute or the volume the class needs, at work height.
- 3. Enter the highest location's reading, or the 95% UCL the counter software reports.
Tools: a laser particle counter (0.3 or 0.5 µm channel), calibrated within a year
Sources: ISO 14644-1:2015, Classification of air cleanliness by particle concentration (Table 1 and Annex A); Federal Standard 209E (withdrawn 2001, still used in names). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- What ISO class is a Class 10,000 cleanroom?
- ISO 7. Class 10,000 meant 10,000 particles of 0.5 µm per cubic foot, which is 352,000 per cubic meter, the ISO 7 limit. Class 100 is ISO 5 and Class 100,000 is ISO 8, the class most modular cleanrooms for packaging, assembly, and medical device work are built to.
- Which particle size do I classify on?
- Most rooms on 0.5 µm; electronics and pharma rooms also on 0.3 or 0.1. The class is set by the worst size, and ISO 14644-1 limits which sizes may be used for each class (0.1 µm only up to ISO 6, 5 µm only ISO 7 and above).
Related calculators: Cleanroom air changes and FFUs, Cleanroom recovery time, Cleanroom pressure and offset air. All calculators.