Cleanroom pressurization: the offset air a pressure cascade needs

The pressure you want to hold and the leakage paths, door gaps, pass-throughs, and panel joints in; the makeup air that keeps the room positive, and what a door opening does to it.

Read the guide: what the number means and how to use it

  • Leakage through gaps follows the orifice equation: Q (cfm) = 2,610 × A (ft²) × √ΔP (in. w.c.), which is 4,005 × √ΔP × A with a discharge coefficient of 0.65. Offset air = that leakage plus any exhaust the room loses.
  • An open door is a very large orifice: at 0.03 in. w.c. a 3 by 7 door passes about 9,500 cfm, far more than the offset, so the room's pressure collapses until it closes; the velocity across the opening is what keeps particles out.

Need it quoted?

See what the first-year deduction does to the payback on the same purchase.

Section 179

Cleanroom pressure and offset air

leakage cfm289 cfmoffset air289 cfmopen door9,493 cfm

Offset makeup air

289 cfm

289 cfm leakage + 0 cfm exhaust

Pressure

7.5 Pa

0.03 in. w.c.

Air out through the open door

9,493 cfm

452 fpm across the opening; the room drops to near zero until it closes

Total leakage area
92 sq in
Leakage flow
289 cfm

One line for the file or the vendor

0.03 in. w.c. (7.5 Pa), 3 doors at 24 sq in + 20 sq in other, 0 cfm exhaust: offset air 289 cfm; open 36x84 door passes 9493 cfm.

Keep this result, or have it priced

One email with what you asked for. No list, no newsletter.

How it is figured

  • Leakage through gaps follows the orifice equation: Q (cfm) = 2,610 × A (ft²) × √ΔP (in. w.c.), which is 4,005 × √ΔP × A with a discharge coefficient of 0.65. Offset air = that leakage plus any exhaust the room loses.
  • An open door is a very large orifice: at 0.03 in. w.c. a 3 by 7 door passes about 9,500 cfm, far more than the offset, so the room's pressure collapses until it closes; the velocity across the opening is what keeps particles out.

Sources: ASHRAE Handbook, HVAC Applications, Clean Spaces (pressurization and offset airflow); ISO 14644-4, Annex A (pressure differentials 5 to 20 Pa between classified spaces). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.

Questions people ask

How much positive pressure should a cleanroom have?
0.02 to 0.05 in. w.c. (5 to 12.5 Pa) above the next space out, stepping down through an airlock to the plant; ISO 14644-4 suggests 5 to 20 Pa between zones. More than 0.1 makes doors hard to open and whistles through the gaps.
Where does the offset air come from?
The HVAC unit supplies more air than it returns; the difference leaks out through the gaps and keeps the room positive. That makeup air has to be filtered and conditioned, which is why tight construction, gasketed doors, and a sealed ceiling grid save energy every hour the room runs.

Related calculators: Cleanroom air changes and FFUs, Cleanroom recovery time, Cold room door infiltration load. All calculators.