Cleanrooms and dry rooms
Cleanroom pressurization: the offset air a pressure cascade needs
The pressure you want to hold and the leakage paths, door gaps, pass-throughs, and panel joints in; the makeup air that keeps the room positive, and what a door opening does to it.
Read the guide: what the number means and how to use it
- Leakage through gaps follows the orifice equation: Q (cfm) = 2,610 × A (ft²) × √ΔP (in. w.c.), which is 4,005 × √ΔP × A with a discharge coefficient of 0.65. Offset air = that leakage plus any exhaust the room loses.
- An open door is a very large orifice: at 0.03 in. w.c. a 3 by 7 door passes about 9,500 cfm, far more than the offset, so the room's pressure collapses until it closes; the velocity across the opening is what keeps particles out.
Need it quoted?
See what the first-year deduction does to the payback on the same purchase.
Section 179Cleanroom pressure and offset air
Offset makeup air
289 cfm
289 cfm leakage + 0 cfm exhaust
Pressure
7.5 Pa
0.03 in. w.c.
Air out through the open door
9,493 cfm
452 fpm across the opening; the room drops to near zero until it closes
- Total leakage area
- 92 sq in
- Leakage flow
- 289 cfm
One line for the file or the vendor
0.03 in. w.c. (7.5 Pa), 3 doors at 24 sq in + 20 sq in other, 0 cfm exhaust: offset air 289 cfm; open 36x84 door passes 9493 cfm.
How it is figured
- Leakage through gaps follows the orifice equation: Q (cfm) = 2,610 × A (ft²) × √ΔP (in. w.c.), which is 4,005 × √ΔP × A with a discharge coefficient of 0.65. Offset air = that leakage plus any exhaust the room loses.
- An open door is a very large orifice: at 0.03 in. w.c. a 3 by 7 door passes about 9,500 cfm, far more than the offset, so the room's pressure collapses until it closes; the velocity across the opening is what keeps particles out.
Sources: ASHRAE Handbook, HVAC Applications, Clean Spaces (pressurization and offset airflow); ISO 14644-4, Annex A (pressure differentials 5 to 20 Pa between classified spaces). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- How much positive pressure should a cleanroom have?
- 0.02 to 0.05 in. w.c. (5 to 12.5 Pa) above the next space out, stepping down through an airlock to the plant; ISO 14644-4 suggests 5 to 20 Pa between zones. More than 0.1 makes doors hard to open and whistles through the gaps.
- Where does the offset air come from?
- The HVAC unit supplies more air than it returns; the difference leaks out through the gaps and keeps the room positive. That makeup air has to be filtered and conditioned, which is why tight construction, gasketed doors, and a sealed ceiling grid save energy every hour the room runs.
Related calculators: Cleanroom air changes and FFUs, Cleanroom recovery time, Cold room door infiltration load. All calculators.