Cleanrooms and dry rooms
EV battery dry room moisture load and dehumidifier size
Room size, people, door traffic, makeup air, and the dew point in; the water the dehumidifier has to remove each hour by source, and the desiccant airflow to hold the room.
Read the guide: what the number means and how to use it
- Moisture load = people × grams per hour + door openings (air swapped per cycle at about 12 g/kg plant air less the room's ratio) + makeup air (cfm × 1.699 m³/h per cfm × 1.2 kg/m³ × the difference in g/kg) + process release.
- Desiccant airflow = load ÷ (air density × the g/kg the supply air can pick up before it reaches the room's ratio); the supply dew point is what the dehumidifier delivers. Humidity ratios from the dew points over ice.
Need it quoted?
See what the first-year deduction does to the payback on the same purchase.
Section 179Dry room moisture load
Water to remove
41.68 lb/h
18.91 kg/h, 1000 lb a day
Desiccant airflow to hold the room
128,396 cfm
supply at -60°C dew point (0.007 g/kg) into a -40°C room (0.079 g/kg)
Air changes that is
267.5 per hour
- Makeup air is most of the load: pre-cool it to 45°F before the desiccant (cuts it to about 4 g/kg) and keep the room tight so less is needed.
- From makeup air
- 18,253 g/h600 cfm at 15 g/kg
- From people
- 240 g/h
- From door openings
- 365 g/h
- From the process
- 50 g/h
- Room humidity ratio
- 0.079 g/kg
One line for the file or the vendor
60x40x12 ft at -40°C dp: load 41.68 lb/h (18.91 kg/h): makeup 18253 g/h, people 240, doors 365, process 50; desiccant air 128396 cfm at -60°C dp (267.5 ACH).
How it is figured
- Moisture load = people × grams per hour + door openings (air swapped per cycle at about 12 g/kg plant air less the room's ratio) + makeup air (cfm × 1.699 m³/h per cfm × 1.2 kg/m³ × the difference in g/kg) + process release.
- Desiccant airflow = load ÷ (air density × the g/kg the supply air can pick up before it reaches the room's ratio); the supply dew point is what the dehumidifier delivers. Humidity ratios from the dew points over ice.
What to gather
- 1. Headcount at peak and the garment level; the HVAC engineer's figure for occupant moisture, or 40 g/h as a start.
- 2. Door cycles from the door controller counters, and whether the doors are airlocked.
- 3. Makeup air from the exhaust and pressurization design; outside design conditions from ASHRAE for the site, or the pre-cooled coil leaving condition.
Tools: the door counters, the ventilation design, the process moisture release from the material supplier
Sources: Munters and Bry-Air dry room design guides (lithium battery manufacturing, −40°C dew point); ASHRAE Handbook, HVAC Applications, Industrial Drying and Dehumidification. A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- What dew point does a lithium battery dry room need?
- −40°C (0.08 g/kg) for electrode handling, cell stacking, and winding; electrolyte filling and lithium metal anodes run −50 to −60°C. That is about 0.5% relative humidity at 22°C, beyond any refrigeration dehumidifier, so dry rooms run desiccant wheels, usually two stages with pre-cooling.
- What drives the dehumidifier size?
- Makeup air, almost always: a few hundred cfm of summer air carries more water than a dozen people. Pre-cooling the makeup air to 45°F removes three quarters of it before the desiccant sees it; after that, people and door openings set the load, so airlocks and gowning rules are part of the HVAC design.
- How many air changes?
- The desiccant unit recirculates room air through the wheel at 10 to 30 changes an hour to keep the whole room at the dew point, more than the moisture load alone requires; the calculator shows the changes the load needs so you can see which governs.
Related calculators: Dry room dew point converter, Cleanroom air changes and FFUs, Cleanroom pressure and offset air. All calculators.