Cleanrooms and dry rooms · guide
Dry room moisture load: the guide
A dry room's dehumidifier is sized on grams of water per hour, and most of them come in with the makeup air; the calculator shows the load by source so the money goes where the water comes from.
Why this number matters
Holding a room at −40°C dew point means removing every gram of water that enters it: the people breathe and sweat even in full garb, every door opening swaps a slug of plant air, the makeup air that keeps the room pressurized carries the outdoor humidity, and the electrodes and materials give up water as they sit in the dry air. A desiccant wheel dehumidifier delivers air at −60°C dew point or lower, and the airflow it needs is the water load divided by what each pound of that air can pick up on its way back to the room's set point.
The makeup air term is the one to attack. Summer air at 15 grams per kilogram carries two hundred times the water of the room; pre-cooling it to 45°F on a coil before the desiccant takes out three quarters, and a tight room that needs less makeup air cuts it again. After that, people and doors set the load, which is why dry rooms have airlocks, gowning rules, and headcount limits in the HVAC design, not just in the quality plan.
The desiccant airflow the load needs is often less than the 10 to 30 air changes an hour the room needs to stay uniform, so the recirculation rate governs the unit's size and the moisture load governs its regeneration energy. Both numbers belong on the request for quotation.
How it is figured
- Moisture load = people × grams per hour + door openings (air swapped per cycle at about 12 g/kg plant air less the room's ratio) + makeup air (cfm × 1.699 m³/h per cfm × 1.2 kg/m³ × the difference in g/kg) + process release.
- Desiccant airflow = load ÷ (air density × the g/kg the supply air can pick up before it reaches the room's ratio); the supply dew point is what the dehumidifier delivers. Humidity ratios from the dew points over ice.
A worked example
A 60 by 40 by 12 foot room at −40°C with six people, six door openings an hour, 600 cfm of summer makeup air, and 50 grams an hour from the process carries roughly 20 kilograms of water an hour, 93% of it in the makeup air; a −60°C supply needs about 11,000 cfm to hold it, which is 23 air changes, about where the recirculation would be anyway.
The tool's starting values, and what it returns for them:
| Room length | 60 ft |
| Room width | 40 ft |
| Ceiling height | 12 ft |
| Room dew point | -40 °C |
| People in the room | 6 |
| Moisture per person | 40 g/h |
| Door openings per hour | 6 |
| Air exchanged per opening | 150 cu ft |
| Makeup air | 600 cfm |
| Makeup air moisture | 15 g/kg |
| Process and product moisture | 50 g/h |
| Dehumidifier supply dew point | -60 °C |
| Water to remove | 41.68 lb/h |
| Desiccant airflow to hold the room | 128,396 cfm |
| Air changes that is | 267.5 per hour |
| From makeup air | 18,253 g/h |
| From people | 240 g/h |
| From door openings | 365 g/h |
| From the process | 50 g/h |
| Room humidity ratio | 0.079 g/kg |
- Makeup air is most of the load: pre-cool it to 45°F before the desiccant (cuts it to about 4 g/kg) and keep the room tight so less is needed.
What to gather
- Headcount at peak and the garment level; the HVAC engineer's figure for occupant moisture, or 40 g/h as a start.
- Door cycles from the door controller counters, and whether the doors are airlocked.
- Makeup air from the exhaust and pressurization design; outside design conditions from ASHRAE for the site, or the pre-cooled coil leaving condition.
Tools: the door counters, the ventilation design, the process moisture release from the material supplier
Mistakes that catch people
- Sizing the dehumidifier on the room's volume alone and ignoring the makeup air.
- Using the person figure from an office: dry room garb cuts it, hard work doubles it.
- Running the makeup air straight to the desiccant without pre-cooling: the wheel does the coil's job at ten times the energy.
Rules of thumb
- Makeup air is usually most of the load; pre-cool it.
- 25 to 50 grams per hour per gowned person at light work.
- Recirculate 10 to 30 air changes through the desiccant to keep the room uniform.
When to stop calculating and make a call
- Any dry room: the dehumidification system is engineered by the maker (Munters, Bry-Air, and others) from the process data; this calculator frames the conversation.
- The process releases solvent as well as water: that is an exhaust and safety design.
Questions people ask
- What dew point does a lithium battery dry room need?
- −40°C (0.08 g/kg) for electrode handling, cell stacking, and winding; electrolyte filling and lithium metal anodes run −50 to −60°C. That is about 0.5% relative humidity at 22°C, beyond any refrigeration dehumidifier, so dry rooms run desiccant wheels, usually two stages with pre-cooling.
- What drives the dehumidifier size?
- Makeup air, almost always: a few hundred cfm of summer air carries more water than a dozen people. Pre-cooling the makeup air to 45°F removes three quarters of it before the desiccant sees it; after that, people and door openings set the load, so airlocks and gowning rules are part of the HVAC design.
- How many air changes?
- The desiccant unit recirculates room air through the wheel at 10 to 30 changes an hour to keep the whole room at the dew point, more than the moisture load alone requires; the calculator shows the changes the load needs so you can see which governs.
Standards and sources
- Munters and Bry-Air dry room design guides (lithium battery manufacturing, −40°C dew point)
- ASHRAE Handbook, HVAC Applications, Industrial Drying and Dehumidification
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.